Cold-formed steel wall stud calculator
ColdCalc checks a load-bearing or curtain-wall steel stud to AISI S100-24 in the browser. Enter the stud, its height and spacing, the axial loads and the wind pressure; ColdCalc builds the ASCE 7 load combinations, analyses the stud and reports the governing check with its clause, location and combination.
What you get
This is the result for the design the calculator opens on, computed by the ColdCalc engine when this page was built. Change any input in the calculator and it reruns in about a second.
| Check | S100-24 | Ratio | ||
|---|---|---|---|---|
| Axial compression 0.00 ft, 1.2D + 1.6L | §E2, §E3.2, §E4 | 0.15 | OK | |
| Bending, strong axis 6.00 ft, 1.2D + W (Wind suction) + L | §F2.2, §F3.2, §F4 | 0.20 | OK | |
| Shear 0.00 ft, 1.2D + W (Wind pressure) + L | §G2.1 | 0.04 | OK | |
| Axial and bending combined 6.00 ft, 1.2D + W (Wind suction) + L | §H1.2, Eq. H1.2-1 | 0.31 | OK | |
| Bending and shear combined 6.00 ft, 1.2D + W (Wind suction) + L | §H2, Eq. H2-1 | 0.18 | OK | |
| Deflection 6.00 ft, 0.42W (Wind pressure) | Appendix 1 | 0.13 | OK |
600S162-54, Fy = 50 ksi, 12 ft tall, at 16 in. on center. AISI S100-24 LRFD, Direct Strength Method, finite strip buckling. A ratio is demand over available strength, or an interaction value over its limit; 1.00 or less passes.
What it checks
| Check | What it covers | AISI S100-24 |
|---|---|---|
| Axial compression | Global, local and distortional buckling, with the unbraced lengths the bridging gives | §E2, §E3, §E4 |
| Bending | Lateral-torsional, local and distortional buckling of the flange in compression | §F2, §F3, §F4 |
| Axial and bending combined | The interaction equation with the moment amplified for P-δ | §H1.2, §C1.2.1.1 |
| Shear, and bending with shear | Web shear at the tracks and the interaction along the height | §G2, §H2 |
| Deflection | Service wind deflection with the effective moment of inertia | Appendix 1 |
Every check opens to its limit states, each intermediate value with its equation number, and the φ or Ω applied. Strengths come from the Direct Strength Method by default, or the Effective Width Method, in LRFD or ASD.
What you enter
- An SSMA stud such as 600S162-54, or a custom C-section, and its steel grade
- Height and spacing
- Axial dead, live, roof and snow loads from above, without factors
- Wind pressure and suction on the wall
- Bridging spacing, and sheathing on one face, both or none
- Web punchouts, if the stud has them
- Deflection limit, such as L/360 at 0.42W
How to use it
- 1Open the calculator; it starts on a 600S162-54 wall stud, 12 ft tall at 16 in. on center.
- 2Pick your stud from the SSMA list or enter a custom section, then set the height, spacing and bridging.
- 3Enter the axial loads by source and the wind pressure. ColdCalc writes the combinations.
- 4Read the governing ratio, then click any point of the drawing to see every check there with its equations.
- 5Use Compare sizes to find the lightest stud that passes, and PDF report for the calculation package.
Questions
How do you check a steel stud for combined axial load and wind?
Find the available axial strength (AISI S100-24 Chapter E) and bending strength (Chapter F), amplify the wind moment for the P-δ effect of the axial load (Section C1), and add the two ratios with Eq. H1.2-1: P/Pa + Mx/Max ≤ 1.0. ColdCalc does this at every bridging point, support and moment peak under every ASCE 7 combination.
Does the calculator account for bridging and sheathing?
Yes. Bridging sets the unbraced lengths for weak-axis flexural buckling, torsional buckling and lateral-torsional buckling. Sheathing on a face braces the flange it is attached to along the whole height. You choose bridging spacing and sheathing on one face, both or none.
Which load combinations does it use?
ASCE 7-22 or ASCE 7-16, LRFD or ASD, generated from the loads you enter by source, with wind acting both as pressure and as suction. You can also type your own combinations.
Can it check a stud with punchouts?
Yes. Add a line of web holes (standard SSMA punchouts or your own size and spacing) and the compression, bending, shear and web crippling strengths are reduced as AISI S100-24 requires.
Is this the same as a manufacturer's limiting height table?
No. Limiting height tables give one answer for one set of assumptions, and many are for composite walls with gypsum board. ColdCalc checks your stud for your loads, height, bridging and deflection limit as a bare steel member to AISI S100-24.
ColdCalc is a design aid. AISI S100-24 is the governing text, and results must be reviewed by the engineer responsible for the design. How the engine is tested against published examples, SSMA tables and CUFSM results is on the About page.
How the checks work
Cold-formed steel wall stud design example (AISI S100-24, LRFD)
A complete wind-bearing wall stud check to AISI S100-24 and ASCE 7-22: combinations, axial, bending, P-δ, H1.2, shear and deflection, every number computed.
Steel stud limiting heights: what sets them, with a height table
What a limiting height is, how strength and deflection (L/240, L/360, L/600) set it, the assumptions behind any table, and wall stud heights computed to AISI S100-24 for wind.
How to read an SSMA stud designation: 600S162-54 explained
What each part of an SSMA designation like 600S162-54 means: depth, style, flange width and mils, with design thicknesses, lip lengths, bend radii and the section's properties.