Cold-formed steel design glossary
The ideas behind a member check, then every term ColdCalc uses. The same explanations appear in the ⓘ beside each input and result.
Why cold-formed steel is different
Studs, joists and purlins are bent from thin sheet, typically 0.03 to 0.10 in thick. Thin plates buckle at low stress, so the question is rarely “does the steel yield?” but “which way does it buckle first?”. AISI S100 is the North American Specification that answers it.
Three ways to buckle
Local buckling: the flat walls ripple in short waves. Distortional buckling: a flange and its lip rotate about the flange-web corner. Global buckling: the whole member bends sideways or twists between braces. ColdCalc finds the load that triggers each one (the Buckling tab) and the strength that follows from it.
Demand, capacity and the ratio
Each check divides what the member must carry (demand, from your loads) by what it can carry (available strength). A ratio at or below 1.00 passes. The largest ratio governs the design. OK means below 0.90, NEAR 0.90 to 1.00, NG (no good) above 1.00.
LRFD and ASD
Both start from the same nominal strength Rn. LRFD compares factored loads with φRn; ASD compares service-level load combinations with Rn/Ω. Pick the one your load combinations are written for; ColdCalc applies the matching φ or Ω.
DSM and EWM
The Effective Width Method removes the buckled part of each flat plate and works with the remaining “effective” section. The Direct Strength Method uses the buckling loads of the whole section instead. Both are in the Specification; DSM handles any shape.
Where every number comes from
Open any check row to see the limit states, each value with its symbol and equation number, and the φ or Ω applied. The Calculations tab stacks them into a calc sheet you can print.
What the member is
- Wall stud
- A vertical member in a wall: axial load from above plus wind pushing on the wall face.The stud is analysed under every ASCE 7 combination, with wind in both directions (pressure and suction), and checked as a beam-column (H1) with the moment amplified for P-δ, plus shear (G2), bending with shear (H2) and deflection under service wind. Bridging and sheathing set the unbraced lengths.
- Joist or beam
- A floor joist, roof rafter or header: one span or several, with overhangs if needed.Loads go in by source (dead, live, snow...) as pressures times the spacing. ColdCalc checks bending (Chapter F), shear (G2), bending with shear (H2), web crippling at the supports (G5, H3) and deflection under live and total service load, at every critical point.
- Column
- A member carrying axial load, braced at intervals; loads can be eccentric.Checked for yielding and global buckling (E2), local buckling (E3) and distortional buckling (E4). An eccentric load or a load across the column adds bending, and the column is then checked as a beam-column (H1).
- Known forces
- Type the axial force, moments and shear yourself, for example from a frame analysis.Use this when the forces come from other software. ColdCalc checks one unbraced length for the forces you give. The moments should include second-order effects unless you switch on the P-δ amplification.
- Purlin or girt
- A member over several supports, with overhangs, laps and bracing: ColdCalc analyses it and checks it along its length.Like a CFS analysis: you describe the spans, supports, laps and loadings; ColdCalc builds the ASCE 7 load combinations, finds the moment, shear, deflection, torque and bimoment along the member, and checks every critical point (supports, braces, peaks) to AISI S100-24, including bending with torsion (H4) and the R factor of I6.2.1 for uplift.
- Any member
- A member you lay out yourself: spans, overhangs, laps, what each support restrains, hinges, braces anywhere, and loads in any direction.The full member analysis with nothing preset. Each support can hold any of lateral and vertical movement, twist, the two end rotations and warping; hinges release the moment about either axis; braces can sit anywhere. Loads can be line loads over part of the member (uniform or varying), concentrated forces, moments and torques, each in any direction in the plane of the section, so weak-axis and inclined loads are analysed with bending about both axes and torsion. ColdCalc builds the ASCE 7 combinations and checks every critical point to AISI S100-24.
- Connection
- Screws, bolts, power-actuated fasteners or welds joining two parts, checked to Chapter J for the forces on the connection.Every limit state of the chosen kind of connection is checked: for screws, tilting and bearing of the sheets, the screw itself in shear and tension, pull-out and pull-over, combined shear and tension, and the minimum spacing and edge distances; for bolts, bearing, bolt shear and tension and their interaction; for welds, sheet tearing and the weld metal. The strengths are for the whole connection, the number of fasteners times the strength of one.AISI S100-24 Chapter J
Inputs
- What the member is
- Picks the starting drawing, loads and bracing for the kind of member you are designing.Every type with a length is the same analysis underneath: you describe spans, supports, bracing and the loads by source (dead, live, snow, wind); ColdCalc builds the ASCE 7 combinations, analyses the member and checks it along its length. The types only change the starting values and which inputs are shown first. Known forces skips the analysis: you type P, M and V yourself.
- Section source
- Pick a standard SSMA section by name, or type the dimensions of any other shape.
- SSMA designation
- The industry name of a stud, joist or track, which spells out its size.600S162-54 reads: 600 = 6.00 in deep, S = stud or joist with lips (T = track, no lips), 162 = 1-5/8 in flange, 54 = 54 mil minimum steel thickness (1 mil = 0.001 in). ColdCalc builds the exact geometry from the name: design thickness, lip length and bend radius per SSMA.Typical: Walls: 362S162-33, 600S162-54. Floors: 800S200-54, 1000S200-68.
- Shape
- The cross-section family: C, Z, track, hat, eave strut, or any shape drawn element by element.C sections are studs and joists; tracks hold the ends of studs; Z sections are purlins and girts; hats are furring and deck-like members; an eave strut is a C whose top flange slopes with the roof. C and Z can have lips or not, square or angled lips, and unequal flanges. For anything else, draw the section as a table of straight elements, as in CFS.
- Lips
- Whether the flange tips have stiffening lips.A flange without a lip has a free edge (an unstiffened element) and buckles at a much lower stress. Lips make it a stiffened element but bring in distortional buckling.
- Lip angle
- Angle between the lip and its flange: 90° is square to the flange.Purlins often have lips bent at about 45° to 60°, which eases nesting at laps. An inclined lip stiffens the flange less than a square one of the same length. The angle must be between 40° and 140° for the edge stiffener rules of Appendix 1.Typical: 90° for studs and joists; 45° to 60° for many Z purlins.
- Unequal flanges
- Give the second flange and lip their own sizes.Z purlins are often made with one flange slightly wider than the other so that two of them nest at a lap.
- Second flange widthB2
- Width of the other flange, outside to outside (the bottom flange of a C or Z, the sloped top flange of an eave strut).
- Second lip lengthd2
- Length of the lip on the other flange (0 = no lip there).
- Top flange slope
- Slope of the eave strut's top flange, matching the roof.Typical: 1:12 = 4.76°, 2:12 = 9.46°, 4:12 = 18.4°
- Elements
- The section as a chain of straight elements, each with a length, a direction and a role, joined by bends of radius R.This is how CFS takes any shape. Start at one free edge and walk along the section: each row is the next flat element. The direction is measured counter-clockwise from the +x axis (0° right, 90° up, 180° left, 270° down). The role tells the Specification how to treat the element: the web carries shear and web crippling, flanges and lips are compression elements, and lips stiffen the flanges next to them.
- Element length
- Length of the flat element, in the chosen dimension convention.
- Direction
- Direction of the element, counter-clockwise from +x: 0° right, 90° up, 180° left, 270° down.
- Role
- What the element is: web, flange, lip, intermediate stiffener or other.
- Dimensions
- Whether element lengths are measured on the outside faces, the centerline or the inside faces.Outside dimensions match the out-to-out sizes on drawings and catalogs. CFS offers the same three conventions.
- DepthD
- Overall depth of the section, outside to outside.Bending strength grows quickly with depth, so a deeper section is usually the most efficient way to carry more moment.Typical: 3.625 in to 12 in for framing.
- Flange widthB
- Width of each flange, outside to outside.Wider flanges help resist lateral-torsional buckling but, being thin, are more prone to local and distortional buckling.Typical: 1.25 in to 3.5 in.
- Lip lengthd
- The short return at the flange tip that stiffens the flange.Without a lip a flange edge is free and buckles easily. The lip turns it into a stiffened element, but too short a lip lets the flange and lip rotate together: that is distortional buckling (Sections E4 and F4).Typical: 0.188 in to 1.0 in.
- Bottom flange widthbf
- Width of each outstanding bottom flange of the hat.
- Design thicknesst
- Base steel thickness used in calculations, without the zinc coating.Cold-formed members are thin, so thickness drives almost everything: area, stiffness and especially resistance to local buckling, which scales roughly with t². SSMA design thickness is the minimum thickness divided by 0.95.Typical: 0.0346 in (33 mil) to 0.1017 in (97 mil).AISI S100-24 A2.4
- Inside bend radiusR
- Radius on the inside of each bend where flat parts meet.The corners are modeled as true arcs. Large radii reduce the flat widths that buckle; Table B4.1-1 limits R/t.Typical: About 1.5t for heavier gauges (SSMA: the larger of 3/32 in − t/2 and 1.5t).
- Steel grade
- The steel specification, which sets the yield and tensile strengths.Framing is usually ASTM A1003 structural grade: 33 ksi for thinner members and 50 ksi for 54 mil and heavier. Purlins, girts and other sheet products are often ASTM A653 (galvanized), A792 (Al-Zn coated), A1011 (hot-rolled) or A1008 (cold-rolled) structural steel. The list gives each grade's specified minimum Fy and Fu; confirm them against the standard and the mill certificate, or choose Custom. The 80 ksi grades have low elongation, so Section A3.1.3 reduces the strengths most checks may use.AISI S100-24 A3.1
- Yield strengthFy
- Stress at which the steel starts to yield (deform permanently).Sets the upper limit of every strength. For slender members, buckling governs before yield and a higher Fy helps less.Typical: 33 or 50 ksi.AISI S100-24 A3.1
- Tensile strengthFu
- Stress at which the steel breaks in tension.Used for tension rupture and connections. Must be enough above Fy for the ductility the Specification assumes.Typical: 45 ksi (grade 33), 65 ksi (grade 50).AISI S100-24 A3.1
- Design method
- LRFD compares factored loads with φRn; ASD compares service loads with Rn/Ω.Both come from the same nominal strength Rn. LRFD (load and resistance factor design) multiplies loads by load factors and strength by φ < 1. ASD (allowable strength design) uses unfactored load combinations and divides strength by a safety factor Ω > 1. Use the method your building code and load combinations are written for.AISI S100-24 B3.2
- Strength approach
- DSM uses buckling loads of the whole section; EWM reduces each thin plate to an effective width.Thin plates buckle locally long before the member fails. The Effective Width Method (EWM, Appendix 1) removes the buckled part of each plate. The Direct Strength Method (DSM, E3.2/F3.2) uses the elastic buckling load of the entire section instead and handles any shape. Both are equally valid; results differ a little.AISI S100-24 Chapter E, F; Appendix 1
- Elastic buckling
- How the buckling loads are found: a finite strip analysis, or closed-form formulas.Finite strip (FSM, like CUFSM) analyzes the actual section and finds the local, distortional and global buckling loads numerically. Analytical uses the formulas of Appendix 2 §2.3. FSM is general and usually more accurate; analytical is faster.AISI S100-24 Appendix 2
- Member lengthL
- Length between the member's supports, the default for the effective lengths.Typical: Studs 8 to 20 ft; joists 10 to 24 ft.
- HeightL
- Length between the bottom and top supports (the track or the floor and roof framing).Moment from wind grows with L², deflection with L⁴, and the column buckling load falls with 1/L², so height matters a lot.Typical: Studs 8 to 20 ft.
- Ends
- What the bottom and top supports hold: pinned (sideways and twist) or fixed (also rotation and warping).Studs in track and most columns are pinned at both ends. Fixed ends need a moment connection, such as a welded base plate or a member continuous past the support.
- Spacings
- Distance between members; each one carries the load on this width.The line load on one member is the area load (psf) times the spacing.Typical: 12, 16 or 24 in on center.
- Bracing intervalLb
- Distance between the bridging or blocking that holds the member sideways and against twisting.Braces stop the member from buckling sideways (about the weak axis) and from twisting. ColdCalc uses this length for KyLy and KtLt unless you override them. Sheathing alone is not treated as bracing for axial load here; see the continuous flange bracing switch for bending.Typical: 48 in (bridging at quarter or third points).
- Set effective lengths
- Type KxLx, KyLy and KtLt directly instead of deriving them from the span and bracing.Use this for fixed or partially fixed ends (K < 1) or unusual bracing.
- Effective length, strong axisKx Lx
- Buckling length for bending about the strong axis (in the plane of the web).K is the effective length factor: 1.0 for pinned ends. Usually the full span or height.AISI S100-24 Appendix 2 §2.3.1.1
- Effective length, weak axisKy Ly
- Buckling length for sideways (weak-axis) buckling: the distance between lateral braces.AISI S100-24 Appendix 2 §2.3.1.1
- Effective length, torsionKt Lt
- Length over which the member can twist freely: the distance between braces that stop twisting.Open sections like C and Z twist easily; torsional and flexural-torsional buckling often govern studs unless they are braced.AISI S100-24 Appendix 2 §2.3.1.1
- Moment gradient factorCb
- Credit for moment that varies along the unbraced length; 1.0 is always safe.Lateral-torsional buckling is worst when the moment is constant between braces. When it varies, the member is stronger, and Cb > 1 reflects that. Use 1.0 if unsure.Typical: 1.0 (conservative) to about 1.3 for a uniformly loaded segment.AISI S100-24 Appendix 2 §2.3.1.2
- Compression flange continuously braced
- Sheathing or deck fastened to the compression flange prevents lateral-torsional buckling.For a joist with a floor deck screwed to the top flange, the top (compression) flange cannot move sideways, so lateral-torsional buckling is not checked. Local and distortional buckling still are.
- Axial loadP
- Force along the member. Positive is compression (gravity load from above); negative is tension (uplift, or a hanger or brace pulling).Enter the design-level value: factored for LRFD, or the ASD combination for ASD. In tension ColdCalc checks yielding and rupture (Chapter D) and, with bending, the two equations of Section H1.1; there is no P-δ amplification.
- Axial loadP
- Nominal load from above, applied at the top and carried down to the bottom. Positive is compression; negative is uplift (tension).Enter each source separately (dead, live, roof live, snow, wind) without load factors: ColdCalc builds the ASCE 7 combinations. For a stud the load is the reaction of the framing above per stud, for example the roof dead load times the tributary length times the spacing.Typical: Studs 0.2 to 2 kip per source; columns 1 to 20 kip.
- Eccentricity
- Where the axial load acts on the section, measured from the centroid: click the section in the popover or type eₓ and eᵧ. It adds a moment P·e at the top, falling to zero at a pinned bottom.e_y is along the web, toward the top flange (the one sheathing braces on a stud); e_x is across the web, toward the flange tips. A joist or truss bearing on one flange, or a brick ledge, loads a stud eccentrically. A load off the shear center also twists the member.Typical: 0 for concentric loads; half the depth for a load on one flange.
- Wind both ways
- Check each wind load as pressure and as suction, so either flange can be in compression.Wind pushes on a wall and pulls on it, and each direction puts a different flange in compression. With sheathing on one face only, suction leaves the unsheathed flange in compression, braced only by the bridging. Leave this on for walls.
- Strong-axis momentMx
- Required bending moment about the strong axis (bending in the plane of the web).
- Weak-axis momentMy
- Required bending moment about the weak axis (bending in the plane of the flanges).
- ShearV
- Required shear force carried by the web.
- Strong-axis compression side
- Which flange the strong-axis moment compresses: the top (+y) or the bottom.Sections with unequal flanges, hats and angles have different strengths for the two directions of Mx, so the sign matters. For a C or Z with equal flanges both give the same result.
- Weak-axis compression side
- Which side the weak-axis moment compresses: the flange tips (lips) or the web.A C section is not symmetric about its weak axis, so the strength depends on which side is in compression.
- P-δ amplification
- Increase the moment for the extra bending caused by the axial compression acting on the deflected member.A bowed member under axial load bends further (P-δ). Section C1.2.1.1 multiplies the first-order moment by B1 = Cm/(1 − αP/Pe1) ≥ 1. Leave on unless your moments already come from a second-order analysis.AISI S100-24 C1.2.1.1
- Moment coefficientCm
- Shape factor of the moment diagram for P-δ amplification; 1.0 for members with transverse load.AISI S100-24 C1.2.1.1
- Web crippling at supports
- Check the web for local crushing where the member bears on its support.A concentrated reaction on a thin web can crush or fold it. Section G5 gives the strength from tests, depending on bearing length, whether the flange is fastened and where the load is.AISI S100-24 G5
- Bearing lengthN
- Length of the support under the member at each end.Longer bearing spreads the reaction and raises the web crippling strength. The Specification requires N ≥ 3/4 in.Typical: 1.5 to 3.5 in.AISI S100-24 G5
- Flange fastened to support
- Whether the bearing flange is screwed or bolted to the support.A fastened flange is held flat, which raises the web crippling strength.AISI S100-24 G5, Table G5-2
- Spans
- The distances between supports, left to right. Add a span for each bay the member continues over.A member continuous over supports is stiffer and stronger than simple spans, but it has negative moment over the interior supports, where the bottom flange is in compression.
- Cantilever (overhang)
- Length the member extends past the first or last support. 0 for none.An overhang's free end is unbraced, so ColdCalc uses Cb = 1 and an effective length factor of 2.1 there. Deflection is compared with twice the overhang length.
- Support
- What the support restrains: pinned (up-down, sideways and twist), fixed (also rotation and warping), or vertical only.Purlin and joist supports usually hold the member upright (restrain twist) through clips or rafters, so 'Pinned' restrains twist too. 'Vertical only' lets the member move sideways and twist there.
- Lap over the support
- How far the two members overlap into the left and right spans at an interior support. 0 and 0 = one continuous member.Lapped Z purlins are nested and bolted over the support, which makes the member continuous. In the lap both members carry load: ColdCalc adds their stiffness and shares the forces.
- Bracing
- Braces (bridging, blocking or anti-roll) at regular spacing or at fixed points of each span. Each brace stops sideways movement and twist.Braces shorten the unbraced length for weak-axis, torsional and lateral-torsional buckling, and restrain twist, which also reduces the bimoment from torsion.Typical: Wall studs: bridging every 4 ft. Joists: none under a deck, or mid-span blocking.
- Brace spacing
- Distance between braces, starting at each support.Typical: 4 ft for wall-stud bridging.
- Sheathing
- Board fastened to the stud flanges: none, one face, or both faces of the wall.Sheathing screwed to a flange stops that flange moving sideways. On both faces it braces the stud fully against buckling and twisting (AISI S240 sheathing-braced design is not modelled further). On one face, the other flange relies on the bridging when it is in compression, for example under wind suction.
- Deck on the top flange
- Floor or roof deck fastened to the top flange along the whole span.The deck stops the top flange moving sideways, so where it is in compression (gravity load on a simple span) the member is fully braced. Where the bottom flange is in compression (over interior supports, or under uplift) the braces govern.
- Deck also stops twist
- The deck and its fasteners hold the member upright along its length, so it does not twist.A floor deck screwed to each joist restrains rotation as well as sideways movement; torsion from a load off the shear center is then carried by the deck. Turn it off to analyse the twist (bimoment) between braces.
- Braced flange
- The flange attached to deck or sheathing along its length: usually the top flange of a purlin or joist.Where the braced flange is in compression the member is fully braced (no lateral-torsional buckling). Where it is in tension (uplift, or over interior supports) the other flange is unbraced and buckling between braces is checked, or the R factor of Section I6.2.1 is used if you enter one.
- Sheathing restrains sideways movement
- The deck or sheathing stops the member moving sideways along its whole length.Modelled as a continuous lateral restraint. For a Z purlin this carries the sideways thrust that comes from the Z's unsymmetrical shape.
- Inflection points as braces
- Treat the points where the moment changes sign as braced, for lateral-torsional buckling.Near an interior support the bottom flange is in compression and nothing braces it until the next brace. Many designers take the inflection point (zero moment) as a brace point, as CFS allows. S100 does not say so, so ColdCalc leaves it off unless you choose it; the braced length then runs from the support to the inflection point, for each load combination.
- R factor (uplift)
- Reduction factor of Section I6.2.1 for a through-fastened purlin or girt under uplift. 0 = not used.With one flange screwed to the sheathing and the other in compression, S100-24 Section I6.2.1 allows Mn = R·Mno (Eq. I6.2.1-1), where Mno is the strength with local buckling only (Section F3 with Mne = My); distortional buckling is not checked. R depends on the section depth and span conditions (Table I6.2.1-1): typically 0.4 to 0.7. Leave 0 to check lateral-torsional buckling between braces instead.AISI S100-24 I6.2.1
- Insulation thicknessti
- Thickness of uncompressed glass fiber blanket insulation between the sheathing and the purlin. 0 = none.Insulation compressed under the sheathing lets the purlin roll more, so for a simple span S100-24 multiplies R by r = 1.00 − 0.01·ti (ti in inches, Eq. I6.2.1-2). Section I6.2.1(k) covers 0 to 6 in. ColdCalc does not apply r to continuous spans, which the Specification does not ask for.AISI S100-24 I6.2.1
- Roof slope
- Angle of the roof. Gravity loads then act partly along the purlin's flanges, which twists it.Typical: 2:12 = 9.46°, 4:12 = 18.4°
- Where the load acts
- Where loads act on the section unless a load has its own point: on the top flange over the web (deck bearing), at the shear center, or at the centroid.A load that does not pass through the shear center twists the member. For a C-section the shear center is outside the web, so a load on the top flange twists it; for a Z it is at mid-web, so only the sloped component does. Choose 'Shear center' to ignore torsion from the loads. Any single load can act somewhere else: open its direction arrow, or pick it in the Model panel, and click the section where it acts (a hung load on the bottom flange, a bracket on a flange tip, a load through the shear center).
- Include self weight
- Adds the member's own weight to the dead load, acting at its centroid.
- Loading
- A name for this load, shown in the load combinations.
- Load type
- Dead, live, roof live, snow, rain or wind. The type sets the load factors in each combination.All dead loadings act together. Each other loading is combined on its own, so wind pressure and wind uplift (or live load on different spans) give separate combinations.
- Pressure
- Load per unit area, multiplied by the spacing to load the member. Wind: positive toward the member, negative for uplift.
- Concentrated load
- A single load at a point, positive downward (toward the member for wind).
- Direction
- Which way the load pushes, in the plane of the section (0° along +x, 90° up the web, 180° along −x, 270° down the web), and where on the section it acts: click the section in the popover.Angles are measured counter-clockwise from the section's +x axis, the way the section is drawn (web vertical). 'Default' is gravity for dead, live, snow and rain loads (straight down, tilted by the roof slope) and −y for wind. A load at 0° or 180° bends the member about its weak axis; anything in between bends it about both axes, and a load that does not pass through the shear center also twists it. A negative value reverses the direction.
- Kind of load
- A line load over all or part of the member (uniform or varying), a concentrated force, a concentrated moment, or a torque.
- From
- Where the load starts (or acts, for a concentrated load, moment or torque), measured from the left end of the member.
- To
- Where the line load ends, from the left end of the member.
- w, start
- Intensity of the line load where it starts. Make it differ from the end value for a triangular or trapezoidal load.
- w, end
- Intensity of the line load where it ends.
- Moment
- A concentrated moment applied at a point, about the strong (x) or weak (y) axis of the section. Positive follows the right-hand rule about the axis.
- About
- The axis the moment turns about: x, the strong axis (bends the member in the plane of the web), or y, the weak axis.
- Torque
- A twisting moment applied at a point, about the member's length (the shear-center axis). Positive follows the right-hand rule about the member's length, from left to right.
- Restrains
- What the support holds: movement across the web (x) and along it (y), twist, rotation about the strong and weak axes, and warping.Translations and twist act on the shear-center axis. 'Pinned' holds x, y and twist (a clip angle or rafter that keeps the member upright); 'Fixed' holds everything; 'Vertical only' holds y. Any other mix is a custom support: for example a bearing that holds y and twist but lets the member slide sideways, or a moment connection that is fixed for strong-axis bending only.
- Lateral (x)
- Holds movement across the web, the weak-axis direction.
- Vertical (y)
- Holds movement along the web, the strong-axis direction.
- Twist
- Holds rotation about the member's length.
- Strong-axis rotation
- Holds the end rotation for bending about the strong axis: the member is fixed against strong-axis bending there.
- Weak-axis rotation
- Holds the end rotation for bending about the weak axis.
- Warping
- Holds warping of the cross-section (the flanges cannot rotate in opposite directions), as a welded end plate or a continuous member does.
- Web holes
- Punchouts or other holes in the web, at a regular spacing along the member and centered in the web. They lower the compression, bending, shear and web crippling strengths.With the Direct Strength Method the net section enters the local and distortional buckling values and the yield limits (Appendix 2 Section 2.3); with the Effective Width Method the elements next to the holes follow Appendix 1. Shear uses Section G3 at the nearest hole (C-sections) and web crippling the reduction Rc of Section G6 from the clear distance between the bearing and the nearest hole. SSMA studs have 1-1/2 × 4 in. punchouts, typically 24 in. on center.AISI S100-24 G3, G6; Appendix 2 §2.3
- Hole shape
- Slotted (straight sides with round ends, like stud punchouts), circular or rectangular.
- Depth dₕ
- Size of the hole across the web.
- Length Lₕ
- Size of the hole along the member.
- Spacing
- Center-to-center spacing of the holes along the member.
- First hole
- Center of the first hole from the start (left end or bottom) of the member.
- Bearing stiffener
- A stiffener fastened to the web at the support: a compact stiffener (Section G7.1) or a stud or track (Section G7.2). It replaces the web crippling check there.AISI S100-24 G7
- Area Aₛ
- Cross-sectional area of the bearing stiffener.
- Length Lₛₜ
- Length of the bearing stiffener, normally the clear depth between the flanges.
- Radius of gyration r
- Of the stiffener (with the strip of web acting with it) about the axis in the plane of the web; it buckles as a column of length Lₛₜ.
- Stiffener Fᵧₛ
- Yield stress of the stiffener steel.
- Stiffener section
- The SSMA stud or track used as the stiffener (Section G7.2: web depth ≥ 3-1/2 in., t ≥ 0.0329 in., at least three fasteners).
- Full bearing
- The bearing supports both flanges of the stiffener; otherwise Section G7.2(a) halves the strength.
- Kind of connection
- The fastener or weld: each has its own section of Chapter J.
- Shear force V
- Required force in the plane of the parts, on the whole connection (factored for LRFD, service-level combination for ASD).
- Tension force T
- Required force pulling the parts apart, on the whole connection.
- Number of fasteners
- Screws, bolts, pins or welds sharing the forces equally. The strengths shown are for all of them together.
- Thickness
- SSMA thickness designation (mils) with its design thickness, or another thickness typed beside it.
- Design thickness t
- Base steel thickness of the part, without coating.
- Steel
- The part's steel grade; it sets Fy and Fu. Edit them for any other steel.
- Yield stress Fy
- Specified minimum yield stress of the part.
- Tensile strength Fu
- Specified minimum tensile strength of the part; most connection limit states depend on it.
- Screw size
- Nominal size; it sets the diameter d and a typical hex washer head diameter. Check the manufacturer's data.
- Diameter d
- Nominal screw diameter (Section J4: 0.08 in. ≤ d ≤ 0.25 in.).
- Head and washer
- What bears on sheet 1 in tension: the head alone, a solid steel washer, or a domed washer. It sets the pull-over diameter d′w (Section J4.4.2).
- Head diameter dₕ
- Diameter of the screw head (or the integral washer of a hex washer head).
- Washer diameter d_w
- Outside diameter of the steel washer.
- Washer thickness t_w
- Thickness of the steel or domed washer.
- Screw shear strength Pₙᵥₛ
- Nominal shear strength of the screw itself, from the manufacturer or tests (Section J4.3.3). 0 = not checked.
- Screw tension strength Pₙₜₛ
- Nominal tension strength of the screw itself, from the manufacturer or tests (Section J4.4.3). 0 = not checked.
- Spacing s
- Center-to-center distance between fasteners (minimum 3d for screws and bolts).
- Edge distance e
- Distance from the fastener's center to the nearest edge (minimum 1.5d for screws and bolts).
- Eccentrically loaded
- The screws are loaded eccentrically in tension (a clip or angle), which halves the pull-over strength in the combined check of Section J4.5.1.
- Bolt diameter d
- Nominal bolt diameter.
- Bolt grade
- ASTM or SAE grade; it sets the nominal shear and tension stresses of Table J3.3-1.
- Threads
- Whether the threads are in the shear plane, which lowers the bolt's shear strength.
- Hole type
- Standard, oversized or short-slotted holes (Table J3-1); they change the bearing strength and minimum distances.
- Washers
- Washers under both the head and the nut, or on one side or none (Table J3.3.1-2).
- Limit hole deformation
- Also check bearing with consideration of bolt hole deformation (Section J3.3.2), where the deformation matters.
- Fastener type
- Power-actuated fastener shape: simple pin, tapered, top-hat or threaded stud (Section J5).
- Shank diameter dₛ
- Nominal shank diameter of the power-actuated fastener.
- Hardness HRCp
- Rockwell C hardness of the fastener; it sets the fastener's tensile strength (Section J5.2.1).
- Weld length L
- Length of the weld.
- Electrode Fₓₓ
- Tensile strength of the electrode classification (E70: 70 ksi).
- Loading
- Along the weld (longitudinal) or across it (transverse); the strengths differ (Sections J2.6, J2.7).
- Leg w₁
- Fillet weld leg on sheet 1 (0 = not given; the weld throat check needs the legs for t > 0.10 in.).
- Leg w₂
- Fillet weld leg on sheet 2.
- Visible diameter d
- Visible diameter (arc spot) or width (arc seam) of the weld on the outer surface.
- Edge distance
- From the weld's center to the edge of the connected part (0 = not checked, Sections J2.2.1, J2.3.1).
- Flare-groove type
- Flare-bevel (a bend against a flat) or flare-V (two bends).
- Effective throat tₑ
- Effective throat of the groove weld.
- Brace
- A restraint at a point between the supports: a strap, a bridging line, a kicker or a sag rod. Choose what it holds.A brace that holds x and twist is what bridging does; it shortens the unbraced length for flexural-torsional and lateral-torsional buckling. A brace that also holds y acts as an intermediate support.
- At
- Distance of the brace or hinge from the left end of the member.
- Hinge
- A moment release at a point: a bolted splice or a pinned connection that carries shear but no moment about the chosen axis.A hinge for strong-axis bending makes Mx zero there, for weak-axis bending My. Hinges also release warping. A member with too many hinges becomes a mechanism; ColdCalc reports it.
- Releases Mx
- Strong-axis moment is zero at the hinge.
- Releases My
- Weak-axis moment is zero at the hinge.
- Position
- Distance of the load from the left end of the member.
- Bearing on the flange
- Length over which the load bears on the flange. 0 = the load is not delivered through the flange (no web crippling check).A post, a stud or a beam sitting on the flange pushes on the web from one side, so the web can cripple under it (§G5), and bending at the same point combines with it (§H3). Give the length of the bearing plate or member in contact. The load is taken as unfastened; it is two-flange loading when a support or another bearing load on the opposite flange is within 1.5h.Typical: 1.5 to 6 in.AISI S100-24 G5
- Load combinations
- The ASCE 7 edition whose basic combinations are generated.ASCE 7-22 uses strength-level snow loads: 1.0S (or 0.3S with other loads) in LRFD and 0.7S in ASD. ASCE 7-16 uses 1.6S and 0.5S, and 1.0S in ASD. Seismic combinations are not generated.
- Include torsion
- Analyse twisting from loads off the shear center, and check bending with the bimoment (H4).
- Combinations
- Generate the ASCE 7 combinations, or type your own set of load factors.Generated combinations cover every basic ASCE 7 combination of the loadings you entered (seismic is not generated). Your own set is for other codes, special load cases, or factored loads you already have: each combination is a factor for every loading.
- Combination name
- A label for the combination, shown in the results.
- Strength or service
- Strength combinations are checked against the member's strength (LRFD or ASD, from the header); service combinations check deflection.
- Load factor
- Multiplier on this loading in the combination; leave 0 when the loading is not part of it.Typical: LRFD: 1.2 dead, 1.6 live. ASD: 1.0 dead, 1.0 live.
- Set effective length factors
- Replace the automatic K factors (1.0 between braces, 2.1 for an overhang) with your own.K multiplies each unbraced length found from the supports and braces. Use K < 1 only where the ends are truly restrained against rotation, for example a column fixed at its base.
- K, strong axisKx
- Effective length factor for buckling about the strong axis.AISI S100-24 Appendix 2 §2.3.1.1
- K, weak axisKy
- Effective length factor for sideways (weak-axis) buckling between braces.AISI S100-24 Appendix 2 §2.3.1.1
- K, torsionKt
- Effective length factor for twisting between braces.AISI S100-24 Appendix 2 §2.3.1.1
- Live load deflection limit
- Allowed deflection under live load alone, as span / n.Typical: L/360 floors, L/240 roofs
- Total load deflection limit
- Allowed deflection under the other service combinations, as span / n.Typical: L/240, or L/180 for roofs without ceilings
- Deflection limit
- Allowed deflection under service wind (0.42 times the components and cladding pressure), as height / n.IBC Table 1604.3 sets the limit by the wall finish. The 0.42 factor is footnote f of that table.Typical: L/120 flexible finishes, L/240 other brittle finishes, L/360 plaster or stucco (IBC Table 1604.3); L/600 is common practice behind brick veneer
Checks
- Axial compression
- Can the member carry the compression without yielding or buckling?Three things can happen: the whole member buckles (flexural, torsional or flexural-torsional, E2), the thin walls ripple in short waves (local buckling, E3), or the flange and lip rotate as a unit (distortional, E4). The weakest governs.AISI S100-24 Chapter E
- Bending, strong axis
- Can the member carry the moment without yielding or buckling?The limit states are lateral-torsional buckling (the compression flange swings sideways and the member twists, F2), local buckling interacting with it (F3) and distortional buckling of the compression flange (F4).AISI S100-24 Chapter F
- Bending, weak axis
- Can the member carry the weak-axis moment without yielding or buckling?AISI S100-24 Chapter F
- Shear
- Can the web carry the shear without yielding or shear buckling?Deep, thin webs buckle diagonally under shear; the strength depends on the web depth-to-thickness ratio h/t.AISI S100-24 G2
- Shear along the flanges
- Can the flanges carry the sideways shear Vx without yielding or shear buckling?Bending about the weak axis puts the shear Vx in the flanges, as strong-axis bending puts Vy in the web. Section G2 is written for webs; ColdCalc applies Section G2.1 to each flange supported on both edges (lipped flanges), with kv = 5.34. A flange with a free edge (a track or unlipped section) is outside G2, so Vx is not checked there and a warning says so.AISI S100-24 G2.1
- Web crippling
- Can the web carry the support reaction without crushing locally?AISI S100-24 G5
- Bearing stiffener
- Can the stiffener at a support or under a load carry the force into the web? Where a stiffener is given, it replaces the web crippling check there.Section G7.1: a compact stiffener is a short column, Pn = min(Fwy·Ac, Fn·Ab), with a strip of web acting with it. Section G7.2: a stud or track fastened to the web of a C-section under two-flange loading, Pn = 0.7(Pwc + Pno) ≥ Pwc.AISI S100-24 G7
- Axial and bending combined
- Axial load and bending together: P/Pa + Mx/Max + My/May ≤ 1.0.Each action uses up part of the member's capacity. The interaction adds the fractions. Moments are amplified for P-δ when that option is on.AISI S100-24 H1.2
- Axial tension
- Can the member carry the pull without yielding the gross section or rupturing the net section?Yielding of the gross area (D2) and rupture of the net area (D3), the lesser governing. With web punchouts the net area is the gross area less the hole depth times the web thickness; otherwise ColdCalc takes it equal to the gross area. Check bolt holes and the connection itself separately (Chapter J).AISI S100-24 Chapter D
- Tension and bending combined
- Axial tension and bending together; both H1.1 equations must be ≤ 1.0.Eq. H1.1-1 checks the tension side: Mx/Maxt + My/Mayt + T/Ta, with Maxt based on yielding of the tension fiber. Eq. H1.1-2 checks the compression side, where the tension relieves the bending: Mx/Max + My/May − T/Ta. Tension straightens the member, so there is no P-δ amplification.AISI S100-24 H1.1
- Bending and shear combined
- Where both are large, √((M/Maℓo)² + (V/Va)²) ≤ 1.0.Shear and bending stresses combine in the web. ColdCalc checks points along the span with the moment and shear at each point, because the two peak in different places.AISI S100-24 H2
- Weak-axis bending and shear combined
- Where both are large, √((My/Maℓo)² + (Vx/Va)²) ≤ 1.0, with the flanges carrying the shear.The weak-axis counterpart of Eq. H2-1, with the shear strength of the flanges and the local-only weak-axis strength Maℓo. The moment is amplified for P-δ, as in H1.2.AISI S100-24 H2
- Deflection
- Does the member stay stiff enough under service load (Δ ≤ L/n)?A serviceability check: exceeding it does not collapse the member but can crack finishes or feel bouncy.
- Bending and torsion combined
- Bending plus the bimoment from twisting: Mx/Max + My/May + B/Ba ≤ 1.0 (1.25 when the bimoment is favorable).A load that does not pass through the shear center twists the member. Twisting a thin open section warps it, and where warping is restrained the flanges bend in opposite directions: that is the bimoment B. Its stresses add to the bending stresses. Each ratio must also be ≤ 1.0. The limit rises to 1.25 when the bimoment puts the free edges of a C's compression flange (or both flanges of a Z) in tension.AISI S100-24 H4, G8.1
- Bending and web crippling combined
- Over an interior support the web carries the reaction and the moment together (H3).The reaction crushes the web locally while the negative moment compresses it too. Section H3 limits the combination.AISI S100-24 H3
Limit states
- Yielding and global buckling
- The whole member bends sideways or twists as a unit (flexural, torsional or flexural-torsional buckling), or yields.Fn follows from the elastic global buckling stress Fcre and the slenderness λc. Longer unbraced lengths lower it quickly.AISI S100-24 E2
- Local buckling
- The thin walls ripple in short waves, about the width of the element, reducing the strength.Local buckling interacts with global buckling: the strength is found from the global strength and the local buckling load. Thin, wide elements are most affected.AISI S100-24 E3, F3
- Distortional buckling
- A flange and its lip rotate about the flange-web corner, in waves several times the section depth.Specific to cold-formed sections with edge-stiffened flanges. Longer lips and bracing help.AISI S100-24 E4, F4
- Yielding and lateral-torsional buckling
- The compression flange swings sideways and the member twists between braces, or the section yields.Bracing the compression flange closer together (or continuously) raises this strength.AISI S100-24 F2
- Inelastic reserve
- Extra bending strength beyond first yield for compact sections whose elements do not buckle first.AISI S100-24 Chapter F
- Shear
- Shear yielding or shear buckling of the web.AISI S100-24 G2
- Web crippling
- Local crushing of the web under a concentrated load or reaction; strength from Table G5 coefficients.EOF = end one-flange loading: a reaction at the end of the member applied through one flange.AISI S100-24 G5
- Weak-axis buckling, one flange fastened to sheathing
- A C or Z purlin or girt in compression with one flange screwed to the deck or wall panels: its weak-axis strength comes from tests, Pn = C1·C2·C3·A·E/29500.Section I6.2.3 replaces flexural-torsional buckling about the weak axis with an empirical strength for members whose sheathed flange is through-fastened, within conditions (1) to (10) of that section (depth 6 to 12 in., t ≤ 0.125 in., edge-stiffened flanges, span ≤ 33 ft, steel panels with screws at 12 in. or less, and others). Strong-axis buckling is checked by Sections E2 and E3; distortional buckling is excluded. Outside the conditions ColdCalc uses Chapter E with the sheathing as a continuous brace.AISI S100-24 I6.2.3
- Tension
- Yielding of the gross section or rupture of the net section.AISI S100-24 Chapter D
- Cylindrical tube
- Yielding or local buckling of a round tube wall.AISI S100-24 E3.3, F2.3, F3.3
- Bearing stiffener
- Strength of a stiffener added under a concentrated load.AISI S100-24 G7
- Torsion bimoment
- Warping stress from twisting of an open section.AISI S100-24 G8.1
- Weld strength
- A weld fails by the sheet tearing next to it or by the weld metal itself shearing; each is a separate limit state.Sections J2.1 to J2.8 give, for each kind of weld, the strength limited by the connected sheets (which usually governs in thin steel) and, for thicker parts, by the weld throat with the electrode strength Fxx.AISI S100-24 J2
- Bolt bearing
- The sheet crushing or tearing at the bolt hole: C·mf·d·t·Fu (Section J3.3.1), or a lower value where hole deformation matters (Section J3.3.2).AISI S100-24 J3.3
- Bolt shear or tension
- The bolt itself breaking in shear or tension: the nominal stress of its grade times its area (Section J3.4).AISI S100-24 J3.4
- Screw tilting and bearing
- The sheets tearing at the screw or the screw tipping over in the thinner sheet (Section J4.3).For t2/t1 ≤ 1.0 the screw can tilt: Pnv = 4.2(t2³d)^½Fu2, and bearing of each sheet 2.7tdFu also limits it; for t2/t1 ≥ 2.5 only bearing applies; in between the strength is interpolated.AISI S100-24 J4.3
- Screw pull-out or pull-over
- In tension, the threads pulling out of sheet 2 (Section J4.4.1) or sheet 1 pulling over the head or washer (Section J4.4.2).AISI S100-24 J4.4
- Screw strength
- The screw itself breaking in shear or tension; its strength comes from the manufacturer or tests (Sections J4.3.3, J4.4.3).AISI S100-24 J4.3.3, J4.4.3
- Power-actuated fastener
- Limit states of power-actuated fasteners: the fastener in shear or tension, bearing and tilting of the sheet, pull-out and pull-over (Section J5).AISI S100-24 J5
- Rupture of the connected part
- The connected part tearing through its net section: in shear along the fasteners, in tension across them, or a block of it tearing out (Section J6).AISI S100-24 J6
Results
- Governing ratio
- The highest demand-to-capacity ratio of all checks. Below 1.00 the member works.Each check divides what the member must carry (demand) by what it can carry (available strength). The largest ratio decides the design. OK is below 0.90, NEAR is 0.90 to 1.00, NG (no good) is above 1.00.
- Status
- OK below 0.90, NEAR from 0.90 to 1.00, NG (no good) above 1.00.A ratio is never rounded down to pass: 1.004 displays as 1.00 but is still NG.
- Check
- The design requirement being verified, with the Specification section.
- Demand
- What the member has to carry: the required strength from the loads.For LRFD this comes from factored loads; for ASD from service-level load combinations.
- Capacity
- Available strength: φRn for LRFD or Rn/Ω for ASD.Rn is the nominal strength from the Specification. It is reduced by φ (LRFD) or divided by Ω (ASD) for safety.AISI S100-24 B3.2
- Ratio
- Demand divided by capacity (or the interaction value divided by its limit). At most 1.00 to pass.
- Service line loadws
- Service load per unit length used for deflection: service pressure × spacing.
- End reactionR
- Force at each support: wL/2. Used for web crippling.
- P-δ amplifierB1
- Factor applied to the moment for the effect of axial load on the deflected shape. 1.0 means no amplification.AISI S100-24 C1.2.1.1
- DeflectionΔ
- Midspan deflection under the service load: 5wL⁴/(384EIeff).
- Allowed deflectionL/n
- The deflection limit as a length: span divided by n.
- Effective moment of inertiaIeff
- Bending stiffness at the service load, with the locally buckled parts removed.Thin elements buckle even at service loads, which makes the member slightly more flexible than its gross Ix suggests.AISI S100-24 Appendix 1 (serviceability, Procedure I)
- Service momentMs
- Midspan moment under the service load (wₛL²/8), used to find Ieff for deflection.
- Where this was computed
- The member checks ran on ColdCalc's Convex backend, or in your browser.Both run the same engine with the same inputs, so the numbers are identical. ColdCalc uses the Convex backend when it can reach it and falls back to your browser if it cannot, so a check never waits on the network.
- Nominal strengthRn
- The strength from the Specification's equations, before φ or Ω.
- Safety factorΩ
- ASD divides the nominal strength by Ω.AISI S100-24 B3.2.1
- Resistance factorφ
- LRFD multiplies the nominal strength by φ.AISI S100-24 B3.2.2
- Available strength
- φRn (LRFD) or Rn/Ω (ASD) of the governing limit state.
- Limit states
- Every way the member can fail under this load. The weakest one governs.
- Dimensional limits
- Table B4.1-1 limits on width-to-thickness and other ratios for which EWM and DSM were validated.Outside the limits the method is not prequalified; the Specification then requires tests or rational analysis with larger safety factors.AISI S100-24 B4.1, Table B4.1-1
- Source
- Where the buckling value came from: finite strip analysis (FSM), closed-form formulas (analytical), or you.
- Modal participation
- How much of the buckled shape at each half-wavelength is global, distortional, local or other deformation.Constrained finite strip analysis (cFSM) splits the buckled shape into the four mode classes of Ádány and Schafer: global (the section moves as a rigid body), distortional (the cross-section changes shape with the corners moving), local (the walls bend between fixed corners) and other (shear and transverse extension). ColdCalc labels the local and distortional buckling loads by this participation, so a mode is found even where the curve has no distinct low point.
- 3D model
- The member as analysed: the section along each member (laps side by side), what every support and brace holds, hinges, and every load in its direction.Green marks a restraint: a post under the member holds it vertically (y), a strut from the side holds it laterally (x), an arc holds twist, and a filled square fixes rotation or warping. Blue arrows are the nominal loads, before load factors, drawn where they act on the section. The drawing is made from the same arguments the analysis receives.
- Weight
- Steel weight per unit length of member.
- Utilization
- The largest ratio of required to available strength over every action and interaction of the connection; above 1.00 the connection does not work.
- Combined shear and tension
- Interaction of the shear and tension ratios where the Specification requires it (J2.2.4, J3.4, J4.5, J5.4).
- Spacing and edge distance
- The minimum center-to-center spacing and edge distances of the Specification for the fastener or weld.
- Load combination
- The factored sum of the loadings this result is for.Strength combinations (LRFD or ASD) are used for the member checks; service combinations for deflection.
- Location
- Where along the member the check governs, measured from the left end.ColdCalc checks every support, brace, load point and member end (just left and just right, where values jump) and the peaks of moment, bimoment and shear inside each segment.
- Envelope
- The largest and smallest value at each point over all strength combinations.
- Axial forceN
- Force along the member, compression positive. It grows down a stud or column as loads join it.
- Bending momentMx
- Positive compresses the top flange (sagging); negative over interior supports compresses the bottom flange.
- ShearVy
- Force across the member; it jumps at each support by the reaction.
- Deflectionv
- Vertical movement of the member, with gross section properties (negative = down).
- TorqueT
- Twisting moment in the member. Part is carried by St. Venant shear (Tsv), part by warping (Tw).
- BimomentB
- The warping 'moment' from restrained twisting: flanges bending in opposite directions. It gives normal stresses σ = B·ωn/Cw.It peaks where twist is restrained and where concentrated torques act. Units are force × length².AISI S100-24 G8.1
- Twistφ
- Rotation of the section about the shear center, in degrees.
- Reactions
- The forces the supports provide, for the selected combination: vertical, sideways and the torque at twist restraints.
- Unbraced lengths
- KyLy (sideways) and KtLt (twist) of the segment around this point, from the braces and supports.
Elastic buckling
- Global buckling loadPcre
- Axial load at which the whole member buckles elastically: flexural, torsional or flexural-torsional.Depends on the unbraced lengths. The smallest of the global modes is used.AISI S100-24 Appendix 2 §2.3.1.1
- Local buckling loadPcrℓ
- Axial load at which the thin walls first ripple in short waves (local buckling).Found from the section alone; does not depend on the member length. From the finite strip signature curve: its first minimum.AISI S100-24 Appendix 2
- Distortional buckling loadPcrd
- Axial load at which a flange and lip rotate about the corner (distortional buckling).AISI S100-24 Appendix 2
- Local half-wavelengthLcrℓ
- Length of one local buckling wave; roughly the width of the buckling element.
- Distortional half-wavelengthLcrd
- Length of one distortional wave; typically a few times the section depth. Bracing closer than this raises Pcrd and Mcrd.
- Global buckling momentMcre
- Moment at which the member buckles laterally and twists (lateral-torsional buckling), elastically.AISI S100-24 Appendix 2 §2.3.1.2
- Local buckling momentMcrℓ
- Moment at which the compression parts of the section first buckle locally.AISI S100-24 Appendix 2
- Distortional buckling momentMcrd
- Moment at which the compression flange and lip rotate about the corner.AISI S100-24 Appendix 2
- Moment gradient factor, distortionalβ
- Increase in the distortional buckling moment for a moment gradient over the distortional wavelength.AISI S100-24 F4
- Net areaAnet
- Area with holes removed.
- Local buckling load, net sectionPcrℓ,net
- Local buckling load of the section through a hole.
- Distortional buckling load, net sectionPcrd,net
- Distortional buckling load with holes.
- Distortional buckling moment, net sectionMcrd,net
- Distortional buckling moment with holes.
Section properties
- AreaA
- Cross-sectional area of steel. Sets axial yield (Py = A·Fy) and weight.
- Centroid, xxc
- Horizontal position of the centroid from the web centerline datum.
- Centroid, yyc
- Vertical position of the centroid.
- Moment of inertia, xIx
- Resistance to bending about the strong (horizontal) axis. Controls deflection and strong-axis buckling.
- Moment of inertia, yIy
- Resistance to bending about the weak (vertical) axis.
- Product of inertiaIxy
- Zero for sections symmetric about x or y; nonzero for Z sections, whose principal axes are inclined.
- Major principal moment of inertiaI1
- Largest moment of inertia, about the principal axis.
- Minor principal moment of inertiaI2
- Smallest moment of inertia; the axis the member buckles about most easily.
- Principal axis angleθp
- Angle between the x axis and the major principal axis.
- Radius of gyration, xrx
- √(Ix/A). Slenderness for strong-axis buckling is KxLx/rx.
- Radius of gyration, yry
- √(Iy/A). Slenderness for weak-axis buckling is KyLy/ry.
- Radius of gyration, major principalr1
- √(I1/A).
- Radius of gyration, minor principalr2
- √(I2/A).
- Distance to top fiberctop
- From the centroid to the top edge.
- Distance to bottom fibercbot
- From the centroid to the bottom edge.
- Distance to right fibercright
- From the centroid to the right edge.
- Distance to left fibercleft
- From the centroid to the left edge.
- Section modulus, x topSx,top
- Ix / c_top. The moment at first yield of the top fiber is Sx·Fy.
- Section modulus, x bottomSx,bot
- Ix / c_bottom.
- Section modulus, y rightSy,right
- Iy / c_right.
- Section modulus, y leftSy,left
- Iy / c_left.
- Plastic modulus, xZx
- Moment at full plastification about x is Zx·Fy. Used for inelastic reserve.
- Plastic modulus, yZy
- Moment at full plastification about y is Zy·Fy.
- Plastic neutral axis, yypna
- Height of the axis that splits the area in half (bending about x).
- Plastic neutral axis, xxpna
- Position of the axis that splits the area in half (bending about y).
- St. Venant torsion constantJ
- Resistance to uniform twisting. Tiny for thin open sections (about Σ bt³/3), which is why they twist easily.
- Warping constantCw
- Resistance to twisting that comes from the flanges bending in opposite directions (warping). Important for C and Z sections.
- Shear center, x offsetxo
- Horizontal distance from the centroid to the shear center. For a C it lies outside the web, opposite the flanges.Loads not applied through the shear center twist the member; this is why a C section twists under gravity load on its flange.
- Shear center, y offsetyo
- Vertical distance from the centroid to the shear center.
- Polar radius of gyrationro
- √(rx² + ry² + xo² + yo²) about the shear center. Used for torsional buckling.AISI S100-24 Appendix 2 §2.3.1.1
- Monosymmetry parameter, xjx
- Used for lateral-torsional buckling of sections not symmetric about the bending axis.
- Monosymmetry parameter, yjy
- Used for lateral-torsional buckling about y of sections like the C.
- Maximum normalized warping functionωn,max
- Largest warping coordinate; the warping stress from a bimoment B is B·ωn/Cw.
- Centerline lengthLcl
- Total length of the section's centerline (area = length × t for uniform t).
- Weight
- Steel weight per foot (area × 490 lb/ft³).
- Enclosed areaAo
- Area enclosed by a closed cell (tubes); zero for open sections.
Calculation symbols
- Global buckling stressFcre
- Pcre / A: the elastic stress at which the member buckles globally.
- Global slendernessλc
- √(Fy/Fcre). Below 1.5 the member fails inelastically; above, by elastic buckling.AISI S100-24 Eq. E2-4
- Global buckling stress capacityFn
- Nominal stress the member reaches before global buckling (E2-2, E2-3), at most Fy.
- Global compressive strengthPne
- Ag·Fn: nominal strength for yielding and global buckling.AISI S100-24 Eq. E2-1
- Local slendernessλℓ
- √(Pne/Pcrℓ) or √(Mne/Mcrℓ). Above 0.776 local buckling reduces the strength.AISI S100-24 E3.2, F3.2
- Local buckling strengthPnℓ
- Nominal axial strength for local buckling interacting with global buckling.AISI S100-24 E3
- Squash loadPy
- A·Fy: the axial load that yields the whole section.
- Distortional slendernessλd
- √(Py/Pcrd) or √(My/Mcrd). Above 0.561 (compression) or 0.673 (bending) distortional buckling reduces the strength.AISI S100-24 E4, F4
- Distortional buckling strengthPnd
- Nominal axial strength for distortional buckling.AISI S100-24 E4
- Effective areaAe
- Area left after removing the locally buckled parts of each element (Effective Width Method).AISI S100-24 Appendix 1
- Gross areaAg
- Full cross-sectional area.
- Net areaAnet
- Area with holes removed.
- Reduced moment of inertiaIr
- Moment of inertia of a built-up member about the axis that shears its connectors, reduced for the connector spacing.Ir = I·(KL/r)²/((KL/r)² + (a/ri)²), Eq. I1.2.2.1-1, with a the connector spacing and ri the smallest radius of gyration of one shape. It replaces I in the global buckling load.AISI S100-24 I1.2.2.1
- Fastener position coefficientC1
- C1 = 0.79x + 0.54 (Eq. I6.2.3-2).AISI S100-24 I6.2.3
- Thickness coefficientC2
- C2 = 1.17t + 0.93, t in inches (Eq. I6.2.3-3).AISI S100-24 I6.2.3
- Section shape coefficientC3
- C3 = 2.5b − 1.63d + 22.8, b and d in inches (Eq. I6.2.3-4).AISI S100-24 I6.2.3
- Fastener position ratiox
- Where the screws sit across the sheathed flange: a/b for a Z, (b − a)/b for a C, a measured from the outside of the web.ColdCalc assumes screws at mid-flange (x = 0.5) unless the fastener distance is given.AISI S100-24 I6.2.3
- Radius of gyration of one shaperi
- Smallest radius of gyration of one shape of a built-up member.AISI S100-24 I1.2.2.1
- Gross-to-net area ratioAg/Anet
- How much the holes reduce the area.
- Global buckling momentMcre
- Elastic lateral-torsional buckling moment.
- Global flexural strengthMne
- Nominal moment for yielding and lateral-torsional buckling.AISI S100-24 F2
- Yield momentMy
- Sf·Fy: the moment at which the extreme fiber first yields.
- Plastic momentMp
- Z·Fy: the moment with the whole section yielded.
- Local buckling strength, bendingMnℓ
- Nominal moment for local buckling interacting with lateral-torsional buckling.AISI S100-24 F3
- Distortional buckling strength, bendingMnd
- Nominal moment for distortional buckling.AISI S100-24 F4
- Local strength with inelastic reserveMnℓe
- Local buckling strength including inelastic reserve.AISI S100-24 F3
- Global strength for local interactionM̄ne
- The lesser of Mne and My, used in the local buckling equations.
- Nominal flexural strengthMn
- Nominal bending strength.
- Nominal strengthPn
- Nominal axial or concentrated-load strength.
- Effective section modulusSe
- Section modulus of the effective section (buckled parts removed).
- Effective section modulus, compression fiberSec
- Ie / yc of the effective section.
- Effective section modulus, tension fiberSet
- Ie / yt of the effective section.
- Effective moment of inertiaIe
- Moment of inertia of the effective section at the stress Fn.
- Effective neutral axisycg,eff
- Distance from the compression fiber to the effective section's neutral axis.
- Inelastic reserve cap1.25 Se Fy
- Upper limit on the inelastic reserve moment.
- Compression strain factorCy
- Allowed compressive strain beyond yield for inelastic reserve (1 to 3).AISI S100-24 Chapter F
- Strain ratioεcu/εy
- Maximum compressive strain over the yield strain, for inelastic reserve.
- Shape factorks
- Mp/My: how much the plastic moment exceeds first yield. It scales the DSM local buckling strength so stocky sections can reach beyond My.AISI S100-24 Eq. F3.2-3
- Section factorαs
- 1 when a corner lies at the extreme compression fiber (as in a C or Z bent about its strong axis), 0 otherwise. It raises the DSM bending strength of sections whose compression corners do not move in local buckling.AISI S100-24 F3.2, F4
- Symmetry factorβs
- 2yc/d, at least 0.4: the share of the depth in compression. Sections with less of their depth in compression get a higher DSM bending strength.Typical: 1.0 for a C or Z bent about its strong axisAISI S100-24 Eq. F3.2-4
- Moment at the strain limitMy3
- Mp − (Mp − My)/9: the cap on the DSM local and distortional bending strengths, between first yield and the plastic moment.AISI S100-24 Eq. F3.2-5
- Moment at the strain limit, net sectionMy3,net
- My3 of the net section at a hole: the cap on the DSM bending strength of members with holes.AISI S100-24 Eq. F3.2-6
- Gross-to-net modulus ratioSfc/Sfc,net
- How much holes reduce the compression section modulus.
- Shear yield forceVy
- 0.6·Aw·Fy: shear that yields the web.AISI S100-24 Eq. G2.1-3
- Shear buckling coefficientkv
- Plate buckling coefficient for shear: 5.34 for an unreinforced web.AISI S100-24 G2.3
- Shear buckling forceVcr
- Elastic shear force at which the web buckles diagonally.AISI S100-24 Eq. G2.3-1
- Shear slendernessλv
- √(Vy/Vcr). Above about 0.59 shear buckling reduces the strength below Vy (Eq. G2.1-1).AISI S100-24 Eq. G2.1-2
- Nominal shear strengthVn
- Nominal shear strength of the web.AISI S100-24 Eq. G2.1-1
- Hole shear factorαvh
- Reduction of shear strength for a web hole.AISI S100-24 Eq. G3-7
- Equivalent hole depthdh,eq
- Depth of an equivalent hole.AISI S100-24 Eq. G3-9
- Equivalent hole lengthLh,eq
- Length of an equivalent hole.AISI S100-24 Eq. G3-10
- Web crippling coefficientC
- Base coefficient from Table G5 for the section, support and load case.
- Bend radius coefficientCR
- Table G5 coefficient on √(R/t): larger radii lower the strength.
- Bearing length coefficientCN
- Table G5 coefficient on √(N/t): longer bearing raises the strength.
- Web slenderness coefficientCh
- Table G5 coefficient on √(h/t): slender webs cripple more easily.
- Hole reduction factorRc
- Reduction of web crippling strength for a web hole.AISI S100-24 G6
- Overhang factorα
- Increase in end one-flange web crippling strength for an overhang.AISI S100-24 Eq. G5-3
- Web crippling with overhangPnc
- Web crippling strength with the overhang increase.AISI S100-24 Eq. G5-2
- Stiffener effective areaAc
- Effective area of a bearing stiffener.AISI S100-24 G7.1
- Stiffener bearing areaAb
- Bearing area of a stiffener with part of the web.AISI S100-24 G7.1
- Web crippling strengthPwc
- Web crippling strength of the web alone.AISI S100-24 G7.2
- Local strength, bracedPnℓo
- Local buckling strength with global buckling excluded.AISI S100-24 G7.2
- Nominal tensile strengthTn
- Ag·Fy (yielding) or Anet·Fu (rupture).AISI S100-24 D2, D3
- Yield bimomentBy
- Bimoment at which warping stress reaches Fy.AISI S100-24 Eq. G8.1-2
- Plastic bimomentBp
- Fully plastic bimoment Fy·Zw.AISI S100-24 G8.1
- Nominal bimoment strengthBn
- Nominal torsional warping strength.AISI S100-24 G8.1
- Web slenderness, bimomentλw
- Slenderness for web local buckling under bimoment.AISI S100-24 Eq. G8.1-4
- Flange slenderness, bimomentλf
- Slenderness for flange buckling under bimoment.AISI S100-24 Eq. G8.1-6
- Moment ratioM/Ma
- Required moment over available flexural strength.
- Shear ratioV/Va
- Required shear over available shear strength.
- Moment ratio, braced strengthM/Maℓo
- Required moment over the available strength with lateral-torsional buckling excluded (Maℓo), as H2 requires.
- Axial ratioP/Pa
- Required axial force over available axial strength.
- Strong-axis moment ratioMx/Max
- Required strong-axis moment over available strength.
- Weak-axis moment ratioMy/May
- Required weak-axis moment over available strength.
- Tension ratioT/Ta
- Required tension over available tensile strength.AISI S100-24 H1.1
- Strong-axis moment ratio, tension flangeMx/Maxt
- Required moment over the strength based on the tension flange.AISI S100-24 H1.1
- Weak-axis moment ratio, tension flangeMy/Mayt
- Required weak-axis moment over the strength based on the tension side.AISI S100-24 H1.1
- Bimoment ratioB/Ba
- Required bimoment over available bimoment strength.AISI S100-24 H4
- Web crippling ratioP/Pn
- Concentrated load over nominal web crippling strength.
- Moment ratio, H3M/Mnℓo
- Moment over the braced local flexural strength.
- Available moment, bracedMaℓo
- Available flexural strength with lateral-torsional buckling excluded; used in H2 and H3.AISI S100-24 H2
Using ColdCalc
- Units
- Show values in US customary (kip, in, ksi) or SI (kN, mm, MPa).Switching converts every displayed value. The design itself is stored in one set of units, so switching never changes it.
- Guide mode
- Show a one-line explanation under every input, without hovering.