Design examplesIntermediate11 min read

Cold-formed steel wall stud design example (AISI S100-24, LRFD)

A complete wind-bearing wall stud check to AISI S100-24 and ASCE 7-22: combinations, axial, bending, P-δ, H1.2, shear and deflection, every number computed.

By ColdCalc Engineering
In short
  • A wind-bearing wall stud is a beam-column. Check it for axial load (§E2, §E3.2, §E4), bending (§F2, §F3, §F4), the two combined after P-δ amplification (§C1.2.1.1, §H1.2), shear (§G2), bending with shear (§H2) and deflection under service wind.
  • For a 12 ft 600S162-54 stud at 16 in. on center, with 25 psf of wind both ways and 0.4 kip dead plus 0.6 kip live from above, the governing check is axial plus bending at mid-height: 0.31 under 1.2D + W + L.
  • Local buckling of the thin walls limits both strengths: φPn = 9.50 kip and φMn = 37.71 kip·in, against a squash load of 27.8 kip.
  • Deflection under 0.42W is only L/1,860, far inside L/240. This stud has room to go lighter.

Wall studs are the most common cold-formed steel member, and the most common question about them is how to check one for wind and gravity load together. This article works through a complete check of one stud to AISI S100-24 with LRFD and ASCE 7-22 load combinations. Every number on this page comes from ColdCalc's engine, run when the page was built. The stud is the same one the calculator opens with, so you can follow along and change it.

If the designation 600S162-54 is new to you, read how to read an SSMA stud designation first. The design guide gives the bigger picture.

The stud, its loads and its assumptions#

InputValue
Section600S162-54: 6 in. deep, 1-5/8 in. flanges, 54 mil (design thickness 0.0566 in.), Fy = 50 ksi
Height12 ft, pinned at the bottom and top tracks
Spacing16 in. on center
BridgingEvery 4 ft, restraining lateral movement and twist
Axial load0.40 kip dead and 0.60 kip live per stud, concentric, at the top
Wind25 psf, acting inward (pressure) and outward (suction)
DeflectionL/240 under 0.42W
MethodLRFD, Direct Strength Method; local and distortional buckling by finite strip, global buckling by Appendix 2

The wind on one stud is the pressure times the spacing: w = 25 psf × 16/12 ft = 33.3 plf. No sheathing is credited as bracing in this example, so the bridging alone braces the stud. The wind acts through the shear center, so it causes no torsion. Section properties are from the gross cross-section with rounded corners. A = 0.556 in², Ix = 2.860 in⁴, and the stud weighs 1.89 lb/ft.

Load combinations and why wind suction matters#

You enter each load once, unfactored, and by its source. ColdCalc then writes the basic combinations of ASCE 7-22 §2.3.1 that apply: 8 strength combinations and 2 service combinations for deflection.

CombinationP, kipMx, kip·inB1Worst ratio
1.4D0.560.00–0.06
1.2D + 1.6L1.440.00–0.15
1.2D + W (Wind pressure) + L1.087.201.0280.31
1.2D + W (Wind pressure)0.487.201.0120.24
1.2D + W (Wind suction) + L1.087.201.0280.31
1.2D + W (Wind suction)0.487.201.0120.24
0.9D + W (Wind pressure)0.367.201.0090.23
0.9D + W (Wind suction)0.367.201.0090.23
ASCE 7-22 strength combinations generated for the stud, with the axial force, the largest first-order moment Mx, the P-δ amplifier B1 (shown where there is a moment to amplify) and the largest ratio of any check anywhere along the height. Wind pressure and wind suction are separate loadings. Computed by ColdCalc.

Three things are worth seeing in that table:

  1. Axial load alone peaks under 1.2D + 1.6L, at 1.44 kip. Without wind, though, the stud is barely working.
  2. The wind combinations govern. In 1.2D + 1.0W + L the live load drops to its arbitrary-point-in-time factor of 1.0, but the wind moment more than makes up for it. ColdCalc keeps 1.0L in this combination; ASCE 7 permits 0.5L for most occupancies, which ColdCalc does not apply. 0.9D + 1.0W matters for uplift and tension, not here.
  3. Pressure and suction give identical results here. A C-stud is symmetric about its strong axis, and the bridging braces both flanges in the same way. Reversing the wind puts the other flange in compression, and nothing about that flange is different.

Suction matters as soon as the two flanges are braced differently. In a real wall the sheathing on the outside face holds the outer flange continuously, and the inside flange is held only by bridging (or gypsum board, if its bracing is credited). Pressure compresses the sheathed flange, which cannot buckle sideways. Suction compresses the unsheathed one, which can buckle laterally and twist between bridging lines. ColdCalc models sheathing on one face as continuous lateral restraint of that flange, and so it checks suction between the bridging. Components-and-cladding suction near building corners is also often larger than the inward pressure. Check both directions, every time.

The member analysis#

The stud is a single span between pinned supports. Under a uniform load:

  • the moment is largest at mid-height, Mx = wL²/8 = 7.20 kip·in under the full wind;
  • the shear is largest at the tracks, V = wL/2 = 0.20 kip;
  • the axial force is constant over the height, because the load enters at the top.

ColdCalc runs this as a member analysis, not a formula. It checks the stud at the supports, every bridging line, and the peak of each diagram, under every combination. Each location gets its own unbraced lengths. For the middle segment, KxLx = 144 in. (the tracks hold the strong axis), and KyLy = KtLt = 48 in. (the bridging holds the weak axis and twist).

The moment gradient factor Cb comes from the moment diagram between braces (Eq. 2.3.1-8). In the middle segment the moment is almost uniform, so Cb = 1.014. The end segments have smaller moments and a steeper gradient, so a larger Cb, and they never govern here.

Axial strength: three limit states#

S100-24 §E1 makes the axial strength the smallest of three limit states. Every segment of this stud has the same unbraced lengths, so the axial strength is the same all the way up.

Global buckling, §E2

For a C-section, Appendix 2 §2.3.1.1.2 takes the smaller of flexural buckling and flexural-torsional buckling. At this stud's lengths, flexural buckling about the weak axis over the 48 in. between bridging lines gives Pey = 22.81 kip. Flexural-torsional buckling (strong-axis bending coupled with twist) gives 24.77 kip, so the weak-axis mode governs: Pcre = 22.81 kip, and Fcre = Pcre/A = 41.00 ksi.

λc = √(Fy/Fcre) = 1.104; Fn = 0.658λc²Fy = 30.01 ksi; Pne = AgFn = 16.70 kip

Eq. E2-4, E2-2, E2-1

Local buckling interacting with global buckling, §E3.2

The finite strip analysis gives the local buckling load Pcrℓ = 7.80 kip, less than a third of the squash load. S100-24 replaced the S100-16 Direct Strength equations with a rational form:

λℓ = √(Pne/Pcrℓ) = 1.463; Pnℓ = 1.2Pne(1 + 0.10λℓ²)/(1 + 0.55λℓ²) ≤ Pne = 11.17 kip

Eq. E3.2-2, E3.2-1

Distortional buckling, §E4

λd = √(Py/Pcrd) = √(27.82/12.71) = 1.479; Pnd = 1.2Py(1 + 0.05λd²)/(1 + 0.67λd²) ≤ Py = 15.02 kip

Eq. E4-2, E4-1
Limit stateNominal strength
Yielding and global buckling, §E2Pne = 16.70 kip
Local buckling with global buckling, §E3.2Pnℓ = 11.17 kip (governs)
Distortional buckling, §E4Pnd = 15.02 kip

With φc = 0.85, Pa = φcPnℓ = 9.50 kip. The local, distortional and global buckling article explains why the thin walls govern, and the Direct Strength Method article covers the new equations.

Bending strength: yielding, lateral-torsional, local and distortional#

Yielding and lateral-torsional buckling, §F2.2

For a section bent about its axis of symmetry, Appendix 2 gives Mcre = Cbro√(PeyPt) (Eq. 2.3.1.2.1-1), with the weak-axis and torsional buckling loads over the 48 in. between bridging lines. That is 61.75 kip·in with Cb = 1, and 62.58 kip·in with Cb = 1.014. The Direct Strength Method compares it with the plastic moment Mp = ZfFy = 57.03 kip·in:

Mne = Mp(1 − 0.25Mp/Mcre) = 44.04 kip·in

Eq. F2.2-1 (Mcre > 0.5Mp)

That is below the yield moment My = SfFy = 47.67 kip·in. Lateral-torsional buckling between bridging lines already costs strength. Closer bridging, or sheathing that braces the compression flange, would raise it.

Local buckling, §F3.2

The finite strip local buckling moment is Mcrℓ = 72.64 kip·in. S100-24 Eq. F3.2-1 allows some inelastic reserve through ks = Mp/My = 1.196, capped at My3 = Mp − (Mp − My)/9 = 55.99 kip·in. Both flanges have corners at the extreme fibers and the section is symmetric, so αs = βs = 1:

λℓ = √(M̄ne/Mcrℓ) = 0.779; Mnℓ = ksM̄ne(1 + 0.10αsλℓ²)/(1 + 0.55βsλℓ²) = 41.90 kip·in

Eq. F3.2-2, F3.2-1

Here M̄ne is the lesser of Mne and My.

Distortional buckling, §F4

λd = √(My/Mcrd) = √(47.67/68.64) = 0.833; Mnd = Mp(1 + 0.07αsλd²)/(1 + 0.60βsλd²) ≤ My3 = 42.21 kip·in

Eq. F4-2, F4-1

The three are close: Mne = 44.0 kip·in, Mnℓ = 41.9 kip·in and Mnd = 42.2 kip·in. Local buckling gives the lowest, with distortional buckling close behind, so a small change in the section or the bracing could swap them. Max = φbMnℓ = 0.90 × 41.90 kip·in = 37.71 kip·in.

P-δ amplification, §C1.2.1.1#

The axial load acts on a stud that the wind has already bowed, and that adds moment. S100-24 handles it with the amplifier B1 of Eq. C1.2.1.1-3:

B1 = Cm/(1 − αP/Pe1) ≥ 1.0, Pe1 = π²EIx/(KxLx)² = 40.16 kip

Eq. C1.2.1.1-3, C1.2.1.1-5

With transverse load between supports, Cm may conservatively be taken as 1.0 (§C1.2.1.1(b)), and α = 1.00 for LRFD. ColdCalc uses the nominal stiffness EIx, as the effective length method does (§C1.3.1.1). Under 1.2D + W + L, P = 1.08 kip:

B1 = 1/(1 − 1.08/40.16) = 1.028; Mx = B1 × 7.20 = 7.40 kip·in

An increase under 3 % is small, as it usually is for a stud with modest axial load. It grows quickly as P approaches Pe1, so a tall stud with heavy load from above can see a much larger amplification.

Combined axial load and bending, §H1.2#

P/Pa + Mx/Max + My/May = 1.08/9.50 + 7.40/37.71 + 0 = 0.11 + 0.20 = 0.31 ≤ 1.0

Eq. H1.2-1

P and Mx are the required strengths from Chapter C, so Mx is the amplified moment. Pa and Max are evaluated at the location being checked, with that location's unbraced lengths and Cb. The check passes at about a third of capacity, and bending contributes most of it.

Shear, §G2.1, and bending with shear, §H2#

The web's flat depth is h = 5.717 in., so h/t = 101. The shear yield force Vy = 0.6htFy = 9.71 kip (Eq. G2.1-3). The web's elastic shear buckling force, with kv = 5.34 for an unstiffened web, is Vcr = 4.52 kip (Eq. G2.3-1).

λv = √(Vy/Vcr) = 1.466; Vn = 1.2Vy/(1 + 0.57λv²) ≤ Vy = 5.23 kip

Eq. G2.1-2, G2.1-1

With φv = 0.90, Va = 4.71 kip, against V = 0.20 kip. Shear is rarely a concern for studs.

§H2 combines bending and shear: √((M/Mao)² + (V/Va)²) ≤ 1.0 (Eq. H2-1). Mao is the available §F3 strength with Mne = My, the strength of a globally braced member: 40.19 kip·in here. M is the required moment after P-δ amplification, as in §H1.2. Because the moment peaks where the shear is zero, the interaction is largest at mid-height and equals M/Mao = 0.18.

Deflection with the effective moment of inertia#

S100-24 does not set a stud deflection limit. The building code and the wall finish do. The International Building Code permits the components-and-cladding wind to be taken as 0.42 times its value when deflection is checked. That gives a service load of w = 0.42 × 33.3 plf = 14.0 plf and a service moment of 3.02 kip·in.

Cold-formed sections can lose stiffness when their compression elements buckle locally, so S100-24 Chapter L computes deflection with an effective moment of inertia. §L1 takes it from the Appendix 1 effective widths, calculated with the actual service stress fd in place of f (Procedure I of Appendix 1 §1.1(b)). §L2, for the Direct Strength Method, permits Ieff = Ig(Md/M) ≤ Ig instead (Eq. L2-1). ColdCalc uses §L1 with Procedure I. Here the service stress is only about 3.2 ksi, every element is fully effective, and Ieff = Ig = 2.860 in⁴.

Δ = 5wL⁴/(384EIeff) = 0.077 in. = L/1,860 ≤ L/240 = 0.60 in.

Brittle finishes need tighter limits than flexible ones, but this stud would pass even a limit several times stricter.

What governs, and how to go lighter#

CheckClauseRatioWhere
Axial compression§E2, §E3.2, §E40.150.00 ft, 1.2D + 1.6L
Bending, strong axis§F2.2, §F3.2, §F40.206.00 ft, 1.2D + W (Wind suction) + L
Shear§G2.10.040.00 ft, 1.2D + W (Wind pressure) + L
Axial and bending combined§H1.2, Eq. H1.2-10.316.00 ft, 1.2D + W (Wind suction) + L
Bending and shear combined§H2, Eq. H2-10.186.00 ft, 1.2D + W (Wind suction) + L
DeflectionL/240, service0.136.00 ft, 0.42W (Wind pressure)
All checks of the stud, with the largest ratio of each over every location and combination. Computed by ColdCalc.

The stud works at about a third of its capacity, and deflection is not close. That is a sign to try lighter studs. Here is the same wall with thinner and narrower 600-series studs:

StudFy, ksiWeight, lb/ftGoverning ratioCheckL/δ
600S162-54501.890.31§H1.2L/1,860
600S162-43331.520.55§H1.2L/1,506
600S162-33331.170.83§H1.2L/1,166
600S137-43331.410.65§H1.2L/1,328
600S137-33331.080.99§H1.2L/1,029
The same 12 ft wall, loads and bridging with other 600-series studs, at ColdCalc's default grade for each thickness (33 ksi below 54 mil, 50 ksi from 54 mil). L/δ is the deflection under 0.42W, against the L/240 limit. Computed by ColdCalc.

Three things change as the stud gets lighter. The thinner walls buckle locally at lower loads, so strength falls faster than weight. The 33 and 43 mil studs are usually supplied at 33 ksi, not 50 ksi, so they lose strength twice. And deflection grows, though not enough to matter here. The 600S162-33 still has margin, and the 600S137-33 is right at the limit. Beyond strength, the choice comes down to what the rest of the wall needs. That means the connections to the tracks, the track itself, the bridging connections and openings. None of those are in this check.

Bridging, sheathing and what this check does not cover#

The bridging lines are what make KyLy and KtLt 48 in. instead of 144 in. Without them the weak-axis and torsional buckling loads would be computed over the full 144 in., and both the axial and the bending strength would drop sharply. A brace only works if it is strong and stiff enough. S100-24 §C2.3 gives the required strength and stiffness of translational braces for compression members: for example, Prb = 0.01Pra for one concentrically loaded member (Eq. C2.3.1-1), with a separate rule for many parallel members braced together (§C2.3.2). The bridging also has to resist twist and anchor its accumulated force somewhere.

The framing-specific rules are in AISI S240, the North American Standard for Cold-Formed Steel Structural Framing. These include bridging design and the option of crediting sheathing as bracing. AISI S240 is outside ColdCalc's scope. ColdCalc treats each bridging line as a brace point and checks the stud. It does not design the bridging, the clip angles, the sheathing attachment, or the track. Check those separately.

Two more assumptions to keep in mind:

  • Load point. The wind here acts at the shear center. Wind delivered through sheathing screwed to a flange acts off the shear center, which twists a C-stud between braces. ColdCalc can apply load at the flange, and then the warping torsion check of §H4 joins the list.
  • Eccentric axial load. A joist or truss bearing on the top track can load the stud off its centroid. ColdCalc accepts an eccentricity at the top, which adds a moment that runs from P·e at the top to zero at the bottom.

How do you design a cold-formed steel stud for wind and axial load?

Treat it as a beam-column. Generate the ASCE 7 strength combinations with wind in both directions, analyze the stud as a simply supported member, and at each critical location compute the available axial strength (AISI S100-24 Sections E2, E3 and E4) and flexural strength (F2, F3 and F4) using the unbraced lengths set by bridging or sheathing. Amplify the moment for P-delta with B1 (Section C1.2.1.1) and check P/Pa + Mx/Max ≤ 1.0 (Eq. H1.2-1). Then check shear (G2), bending with shear (H2) and deflection under service wind.

What deflection limit should I use for wall studs?

AISI S100 does not set one; the building code and the wall finish do. Brittle finishes such as plaster, stucco or masonry veneer need much stricter limits than flexible ones. The International Building Code permits the components-and-cladding wind to be multiplied by 0.42 when checking deflection. Compute it with the effective moment of inertia of S100-24 Chapter L, which uses the Appendix 1 effective widths at the service stress.

Which load combination governs a wind-bearing wall stud?

Usually the wind combination with gravity, 1.2D + 1.0W + L in ASCE 7-22 strength design, at mid-height. The 1.2D + 1.6L combination gives the largest axial force but no bending. Check wind suction as well as pressure: when sheathing braces only the outside flange, suction puts the unbraced inside flange in compression.

Does bridging spacing affect stud strength?

Yes. Bridging sets the weak-axis and torsional unbraced lengths, which control flexural-torsional buckling in compression and lateral-torsional buckling in bending. Closer bridging raises both. The bridging itself must have the strength and stiffness required by AISI S100-24 Section C2.3 and the framing standard AISI S240.

What is B1 in cold-formed steel stud design?

B1 is the P-delta amplifier of AISI S100-24 Eq. C1.2.1.1-3, B1 = Cm/(1 - alpha P/Pe1). It increases the first-order moment for the extra bending caused by axial load acting on the bowed member. For typical studs it is a few percent, but it grows quickly as the axial load approaches the strong-axis buckling load Pe1.