250S162-68 stud properties and strength

SSMA 2-1/2 in stud or joist, 1-5/8 in flange, 68 mil (0.0713 in), Grade 50 (ASTM A1003 ST50H). Gross and effective properties, finite strip buckling loads and available strengths to AISI S100-24, computed by the ColdCalc engine.

The 250S162-68 has an area of 0.443 in² and weighs 1.51 lb/ft. Its strong-axis moment of inertia is 0.450 in⁴ gross and 0.450 in⁴ effective at yield, and its effective section modulus is 0.360 in³. With the flange braced, its allowable moment is 10.8 kip·in (ASD), governed by distortional buckling (§F4).

2-1/2″1-5/8″0.5″ lipt = 0.0713″

Dimensions

Depth2-1/2in
Flange width1-5/8in
Lip length0.5in
Design thickness0.0713in
Minimum thickness0.0677in
Inside bend radius0.1070in
Yield stress Fy50ksi
Tensile strength Fu65ksi

Gross properties

Area A0.443in²
Weight1.51lb/ft
Ix0.450in⁴
Sx0.360in³
rx1.008in
Iy0.162in⁴
Sy0.162in³
ry0.605in

Torsion and effective section

J0.752×10⁻³ in⁴
Cw0.249in⁶
xo-1.422in
ro1.845in
β0.406
Ixe at yield0.450in⁴
Sxe0.360in³

Effective properties: AISI S100-24 Appendix 1, strong-axis bending with the extreme fiber at Fy.

Available strength (AISI S100-24)

ActionNominalASD, Rn/ΩLRFD, φRnGoverned by
Strong-axis moment, flange braced (DSM)18.0210.7916.22§F4 · kip·in
Strong-axis moment, flange braced (EWM)18.0110.7816.21§F2.1 · kip·in
Shear, web without holes4.582.754.13§G2.1 · kip
Axial, 8 ft tall, braced at 4 ft (DSM)8.084.496.87§E2 · kip
Axial, 9 ft tall, braced at 4 ft (DSM)7.504.166.37§E2 · kip
Axial, 10 ft tall, braced at 4 ft (DSM)6.763.755.74§E2 · kip
Axial, 12 ft tall, braced at 4 ft (DSM)5.192.894.42§E2 · kip
Axial, 14 ft tall, braced at 4 ft (DSM)3.952.203.36§E2 · kip
Axial, 16 ft tall, braced at 4 ft (DSM)3.071.712.61§E2 · kip

Axial: pinned ends, weak-axis and torsional bracing every 48 in, concentric load. No holes. Bending and axial load together, unbraced flanges, web crippling and deflection depend on the member: check them in the calculator.

Elastic buckling

0.00.51.01.52.02.53.03.54.04.55.05.51101001000half-wavelength, in (log scale)load factor (P/Py)Local2.47 at 2.0 inDistortional2.03 at 11.2 in
Signature curve of the 250S162-68 in pure compression: the elastic buckling load, as a multiple of the yield load Py, at each buckle half-wavelength. The marked points are the local (Pcrℓ) and distortional (Pcrd) buckling loads, each a minimum of the curve. The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.
0.00.51.01.52.02.53.03.54.04.55.05.56.06.57.07.58.08.59.09.510.010.511.011.512.012.513.01101001000half-wavelength, in (log scale)load factor (M/My)Local5.77 at 1.5 inDistortional3.27 at 10.5 in
Signature curve of the 250S162-68 in strong-axis bending: the elastic buckling load, as a multiple of the yield moment My, at each buckle half-wavelength. The marked points are the local (Mcrℓ) and distortional (Mcrd) buckling loads, each a minimum of the curve. The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.

Finite strip results

Py22.17kip
Pcrℓ at 2.054.73kip
Pcrd at 11.245.08kip
My18.01kip·in
Mcrℓ at 1.5103.91kip·in
Mcrd at 10.558.92kip·in

Signature curve minima, labelled by modal participation (cFSM). Half-wavelengths in inches.

Local
54.73 kip at 2.0 in
Distortional
45.08 kip at 11.2 in
Buckled shapes of the 250S162-68 in compression, from the same finite strip analysis. Local buckling ripples the flat walls with the corners staying put; distortional buckling rotates a flange and its lip about the web–flange corner.

Quick answers

What does 250S162-68 mean?

250S162-68 is an SSMA designation: 2-1/2 in stud or joist, 1-5/8 in flange, 68 mil (0.0713 in). The first number is the depth in hundredths of an inch, the letter is the style (S for a stud or joist with lips, T for track), the next number is the flange width in hundredths of an inch, and the last is the minimum thickness in mils. The design thickness is 0.0713 in.

What are the section properties of a 250S162-68 stud?

Area 0.443 in², weight 1.51 lb/ft, Ix 0.450 in⁴, Sx 0.360 in³, rx 1.008 in, Iy 0.162 in⁴, ry 0.605 in, J 0.752 ×10⁻³ in⁴, Cw 0.249 in⁶, computed by ColdCalc with rounded corners.

What is the allowable moment of a 250S162-68?

With the compression flange braced against lateral-torsional buckling and Fy = 50 ksi, AISI S100-24 gives a nominal strong-axis moment of 18.0 kip·in by the Direct Strength Method (governed by §F4): 10.8 kip·in allowable (ASD) or 16.2 kip·in design strength (LRFD). Unbraced lengths, holes and combined loads reduce it.

What are the local and distortional buckling loads of a 250S162-68?

By finite strip analysis, local buckling in compression occurs at 54.73 kip (half-wavelength 2.0 in) and distortional buckling at 45.08 kip (11.2 in), against a squash load Py of 22.17 kip.

Other 2-1/2 in studs

Computed by the ColdCalc engine from the SSMA dimensions (design thickness, lip length and bend radius as in the SSMA conventions), E = 29,500 ksi, with rounded corners. Manufacturers' published values can differ slightly in rounding and corner modelling; ColdCalc's effective section modulus is within 3 % of the SSMA tables for all 775 studs and tracks compared. Results must be reviewed by a qualified engineer. Validation