250S125-27 stud properties and strength

SSMA 2-1/2 in stud or joist, 1-1/4 in flange, 27 mil (0.0283 in), Grade 33 (ASTM A1003 ST33H). Gross and effective properties, finite strip buckling loads and available strengths to AISI S100-24, computed by the ColdCalc engine.

The 250S125-27 has an area of 0.144 in² and weighs 0.49 lb/ft. Its strong-axis moment of inertia is 0.147 in⁴ gross and 0.131 in⁴ effective at yield, and its effective section modulus is 0.098 in³. With the flange braced, its allowable moment is 1.8 kip·in (ASD), governed by distortional buckling (§F4).

2-1/2″1-1/4″0.188″ lipt = 0.0283″

Dimensions

Depth2-1/2in
Flange width1-1/4in
Lip length0.188in
Design thickness0.0283in
Minimum thickness0.0269in
Inside bend radius0.0796in
Yield stress Fy33ksi
Tensile strength Fu45ksi

Gross properties

Area A0.144in²
Weight0.49lb/ft
Ix0.147in⁴
Sx0.118in³
rx1.009in
Iy0.027in⁴
Sy0.031in³
ry0.434in

Torsion and effective section

J0.039×10⁻³ in⁴
Cw0.031in⁶
xo-0.888in
ro1.413in
β0.605
Ixe at yield0.131in⁴
Sxe0.098in³

Effective properties: AISI S100-24 Appendix 1, strong-axis bending with the extreme fiber at Fy.

Available strength (AISI S100-24)

ActionNominalASD, Rn/ΩLRFD, φRnGoverned by
Strong-axis moment, flange braced (DSM)3.031.822.73§F4 · kip·in
Strong-axis moment, flange braced (EWM)3.031.822.73§F4 · kip·in
Shear, web without holes1.010.610.91§G2.1 · kip
Axial, 8 ft tall, braced at 4 ft (DSM)1.680.931.43§E3.2 · kip
Axial, 9 ft tall, braced at 4 ft (DSM)1.660.921.41§E3.2 · kip
Axial, 10 ft tall, braced at 4 ft (DSM)1.630.911.39§E3.2 · kip
Axial, 12 ft tall, braced at 4 ft (DSM)1.490.831.27§E3.2 · kip
Axial, 14 ft tall, braced at 4 ft (DSM)1.250.701.07§E2 · kip
Axial, 16 ft tall, braced at 4 ft (DSM)0.990.550.84§E2 · kip

Axial: pinned ends, weak-axis and torsional bracing every 48 in, concentric load. No holes. Bending and axial load together, unbraced flanges, web crippling and deflection depend on the member: check them in the calculator.

Elastic buckling

0.00.51.01.52.01101001000half-wavelength, in (log scale)load factor (P/Py)Local0.59 at 2.0 inDistortional0.69 at 7.6 in
Signature curve of the 250S125-27 in pure compression: the elastic buckling load, as a multiple of the yield load Py, at each buckle half-wavelength. The marked points are the local (Pcrℓ) and distortional (Pcrd) buckling loads, each a minimum of the curve. The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.
0.00.51.01.52.02.53.03.54.04.55.01101001000half-wavelength, in (log scale)load factor (M/My)Local2.14 at 1.4 inDistortional1.08 at 7.1 in
Signature curve of the 250S125-27 in strong-axis bending: the elastic buckling load, as a multiple of the yield moment My, at each buckle half-wavelength. The marked points are the local (Mcrℓ) and distortional (Mcrd) buckling loads, each a minimum of the curve. The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.

Finite strip results

Py4.76kip
Pcrℓ at 2.02.81kip
Pcrd at 7.63.27kip
My3.88kip·in
Mcrℓ at 1.48.31kip·in
Mcrd at 7.14.19kip·in

Signature curve minima, labelled by modal participation (cFSM). Half-wavelengths in inches.

Local
2.81 kip at 2.0 in
Distortional
3.27 kip at 7.6 in
Buckled shapes of the 250S125-27 in compression, from the same finite strip analysis. Local buckling ripples the flat walls with the corners staying put; distortional buckling rotates a flange and its lip about the web–flange corner.

Quick answers

What does 250S125-27 mean?

250S125-27 is an SSMA designation: 2-1/2 in stud or joist, 1-1/4 in flange, 27 mil (0.0283 in). The first number is the depth in hundredths of an inch, the letter is the style (S for a stud or joist with lips, T for track), the next number is the flange width in hundredths of an inch, and the last is the minimum thickness in mils. The design thickness is 0.0283 in.

What are the section properties of a 250S125-27 stud?

Area 0.144 in², weight 0.49 lb/ft, Ix 0.147 in⁴, Sx 0.118 in³, rx 1.009 in, Iy 0.027 in⁴, ry 0.434 in, J 0.039 ×10⁻³ in⁴, Cw 0.031 in⁶, computed by ColdCalc with rounded corners.

What is the allowable moment of a 250S125-27?

With the compression flange braced against lateral-torsional buckling and Fy = 33 ksi, AISI S100-24 gives a nominal strong-axis moment of 3.0 kip·in by the Direct Strength Method (governed by §F4): 1.8 kip·in allowable (ASD) or 2.7 kip·in design strength (LRFD). Unbraced lengths, holes and combined loads reduce it.

What are the local and distortional buckling loads of a 250S125-27?

By finite strip analysis, local buckling in compression occurs at 2.81 kip (half-wavelength 2.0 in) and distortional buckling at 3.27 kip (7.6 in), against a squash load Py of 4.76 kip.

Other 2-1/2 in studs

Computed by the ColdCalc engine from the SSMA dimensions (design thickness, lip length and bend radius as in the SSMA conventions), E = 29,500 ksi, with rounded corners. Manufacturers' published values can differ slightly in rounding and corner modelling; ColdCalc's effective section modulus is within 3 % of the SSMA tables for all 775 studs and tracks compared. Results must be reviewed by a qualified engineer. Validation