250S137-30 stud properties and strength

SSMA 2-1/2 in stud or joist, 1-3/8 in flange, 30 mil (0.0312 in), Grade 33 (ASTM A1003 ST33H). Gross and effective properties, finite strip buckling loads and available strengths to AISI S100-24, computed by the ColdCalc engine.

The 250S137-30 has an area of 0.178 in² and weighs 0.61 lb/ft. Its strong-axis moment of inertia is 0.184 in⁴ gross and 0.177 in⁴ effective at yield, and its effective section modulus is 0.137 in³. With the flange braced, its allowable moment is 2.6 kip·in (ASD), governed by distortional buckling (§F4).

2-1/2″1-3/8″0.375″ lipt = 0.0312″

Dimensions

Depth2-1/2in
Flange width1-3/8in
Lip length0.375in
Design thickness0.0312in
Minimum thickness0.0296in
Inside bend radius0.0782in
Yield stress Fy33ksi
Tensile strength Fu45ksi

Gross properties

Area A0.178in²
Weight0.61lb/ft
Ix0.184in⁴
Sx0.147in³
rx1.017in
Iy0.048in⁴
Sy0.053in³
ry0.517in

Torsion and effective section

J0.058×10⁻³ in⁴
Cw0.066in⁶
xo-1.143in
ro1.615in
β0.499
Ixe at yield0.177in⁴
Sxe0.137in³

Effective properties: AISI S100-24 Appendix 1, strong-axis bending with the extreme fiber at Fy.

Available strength (AISI S100-24)

ActionNominalASD, Rn/ΩLRFD, φRnGoverned by
Strong-axis moment, flange braced (DSM)4.392.633.95§F4 · kip·in
Strong-axis moment, flange braced (EWM)4.392.633.95§F4 · kip·in
Shear, web without holes1.190.711.07§G2.1 · kip
Axial, 8 ft tall, braced at 4 ft (DSM)2.481.382.10§E3.2 · kip
Axial, 9 ft tall, braced at 4 ft (DSM)2.421.352.06§E3.2 · kip
Axial, 10 ft tall, braced at 4 ft (DSM)2.341.301.99§E3.2 · kip
Axial, 12 ft tall, braced at 4 ft (DSM)2.021.121.72§E3.2 · kip
Axial, 14 ft tall, braced at 4 ft (DSM)1.590.891.35§E2 · kip
Axial, 16 ft tall, braced at 4 ft (DSM)1.250.691.06§E2 · kip

Axial: pinned ends, weak-axis and torsional bracing every 48 in, concentric load. No holes. Bending and axial load together, unbraced flanges, web crippling and deflection depend on the member: check them in the calculator.

Elastic buckling

0.00.51.01.52.02.53.01101001000half-wavelength, in (log scale)load factor (P/Py)Local0.71 at 2.0 inDistortional1.18 at 13.1 in
Signature curve of the 250S137-30 in pure compression: the elastic buckling load, as a multiple of the yield load Py, at each buckle half-wavelength. The marked points are the local (Pcrℓ) and distortional (Pcrd) buckling loads, each a minimum of the curve. The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.
0.00.51.01.52.02.53.03.54.04.55.01101001000half-wavelength, in (log scale)load factor (M/My)Local2.20 at 1.3 inDistortional1.92 at 12.0 in
Signature curve of the 250S137-30 in strong-axis bending: the elastic buckling load, as a multiple of the yield moment My, at each buckle half-wavelength. The marked points are the local (Mcrℓ) and distortional (Mcrd) buckling loads, each a minimum of the curve. The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.

Finite strip results

Py5.88kip
Pcrℓ at 2.04.18kip
Pcrd at 13.16.96kip
My4.86kip·in
Mcrℓ at 1.310.68kip·in
Mcrd at 12.09.36kip·in

Signature curve minima, labelled by modal participation (cFSM). Half-wavelengths in inches.

Local
4.18 kip at 2.0 in
Distortional
6.96 kip at 13.1 in
Buckled shapes of the 250S137-30 in compression, from the same finite strip analysis. Local buckling ripples the flat walls with the corners staying put; distortional buckling rotates a flange and its lip about the web–flange corner.

Quick answers

What does 250S137-30 mean?

250S137-30 is an SSMA designation: 2-1/2 in stud or joist, 1-3/8 in flange, 30 mil (0.0312 in). The first number is the depth in hundredths of an inch, the letter is the style (S for a stud or joist with lips, T for track), the next number is the flange width in hundredths of an inch, and the last is the minimum thickness in mils. The design thickness is 0.0312 in.

What are the section properties of a 250S137-30 stud?

Area 0.178 in², weight 0.61 lb/ft, Ix 0.184 in⁴, Sx 0.147 in³, rx 1.017 in, Iy 0.048 in⁴, ry 0.517 in, J 0.058 ×10⁻³ in⁴, Cw 0.066 in⁶, computed by ColdCalc with rounded corners.

What is the allowable moment of a 250S137-30?

With the compression flange braced against lateral-torsional buckling and Fy = 33 ksi, AISI S100-24 gives a nominal strong-axis moment of 4.4 kip·in by the Direct Strength Method (governed by §F4): 2.6 kip·in allowable (ASD) or 4.0 kip·in design strength (LRFD). Unbraced lengths, holes and combined loads reduce it.

What are the local and distortional buckling loads of a 250S137-30?

By finite strip analysis, local buckling in compression occurs at 4.18 kip (half-wavelength 2.0 in) and distortional buckling at 6.96 kip (13.1 in), against a squash load Py of 5.88 kip.

Other 2-1/2 in studs

Computed by the ColdCalc engine from the SSMA dimensions (design thickness, lip length and bend radius as in the SSMA conventions), E = 29,500 ksi, with rounded corners. Manufacturers' published values can differ slightly in rounding and corner modelling; ColdCalc's effective section modulus is within 3 % of the SSMA tables for all 775 studs and tracks compared. Results must be reviewed by a qualified engineer. Validation