250S125-68 stud properties and strength

SSMA 2-1/2 in stud or joist, 1-1/4 in flange, 68 mil (0.0713 in), Grade 50 (ASTM A1003 ST50H). Gross and effective properties, finite strip buckling loads and available strengths to AISI S100-24, computed by the ColdCalc engine.

The 250S125-68 has an area of 0.346 in² and weighs 1.18 lb/ft. Its strong-axis moment of inertia is 0.334 in⁴ gross and 0.332 in⁴ effective at yield, and its effective section modulus is 0.264 in³. With the flange braced, its allowable moment is 7.8 kip·in (ASD), governed by distortional buckling (§F4).

2-1/2″1-1/4″0.188″ lipt = 0.0713″

Dimensions

Depth2-1/2in
Flange width1-1/4in
Lip length0.188in
Design thickness0.0713in
Minimum thickness0.0677in
Inside bend radius0.1070in
Yield stress Fy50ksi
Tensile strength Fu65ksi

Gross properties

Area A0.346in²
Weight1.18lb/ft
Ix0.334in⁴
Sx0.268in³
rx0.984in
Iy0.058in⁴
Sy0.065in³
ry0.408in

Torsion and effective section

J0.586×10⁻³ in⁴
Cw0.061in⁶
xo-0.829in
ro1.350in
β0.623
Ixe at yield0.332in⁴
Sxe0.264in³

Effective properties: AISI S100-24 Appendix 1, strong-axis bending with the extreme fiber at Fy.

Available strength (AISI S100-24)

ActionNominalASD, Rn/ΩLRFD, φRnGoverned by
Strong-axis moment, flange braced (DSM)12.967.7611.67§F4 · kip·in
Strong-axis moment, flange braced (EWM)12.967.7611.66§F4 · kip·in
Shear, web without holes4.582.754.13§G2.1 · kip
Axial, 8 ft tall, braced at 4 ft (DSM)5.933.295.04§E2 · kip
Axial, 9 ft tall, braced at 4 ft (DSM)5.593.104.75§E2 · kip
Axial, 10 ft tall, braced at 4 ft (DSM)5.082.824.32§E2 · kip
Axial, 12 ft tall, braced at 4 ft (DSM)3.912.173.32§E2 · kip
Axial, 14 ft tall, braced at 4 ft (DSM)2.961.642.51§E2 · kip
Axial, 16 ft tall, braced at 4 ft (DSM)2.291.271.95§E2 · kip

Axial: pinned ends, weak-axis and torsional bracing every 48 in, concentric load. No holes. Bending and axial load together, unbraced flanges, web crippling and deflection depend on the member: check them in the calculator.

Elastic buckling

0.00.51.01.52.02.53.03.54.04.55.05.51101001000half-wavelength, in (log scale)load factor (P/Py)Local (by cFSM)2.38 at 1.9 inDistortional1.65 at 4.5 in
Signature curve of the 250S125-68 in pure compression: the elastic buckling load, as a multiple of the yield load Py, at each buckle half-wavelength. The marked points are the local (Pcrℓ) and distortional (Pcrd) buckling loads; the distortional mode has no distinct minimum here, so it was identified by its modal participation (cFSM). The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.
0.00.51.01.52.02.53.03.54.04.55.05.56.06.57.07.58.08.59.09.510.010.511.011.512.012.513.013.514.014.51101001000half-wavelength, in (log scale)load factor (M/My)Local (by cFSM)6.46 at 1.2 inDistortional2.52 at 4.0 in
Signature curve of the 250S125-68 in strong-axis bending: the elastic buckling load, as a multiple of the yield moment My, at each buckle half-wavelength. The marked points are the local (Mcrℓ) and distortional (Mcrd) buckling loads; the distortional mode has no distinct minimum here, so it was identified by its modal participation (cFSM). The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.

Finite strip results

Py17.28kip
Pcrℓ at 1.941.05kip
Pcrd at 4.528.55kip
My13.38kip·in
Mcrℓ at 1.286.37kip·in
Mcrd at 4.033.66kip·in

Signature curve minima, labelled by modal participation (cFSM). Half-wavelengths in inches.

Local
41.05 kip at 1.9 in
Distortional
28.55 kip at 4.5 in
Buckled shapes of the 250S125-68 in compression, from the same finite strip analysis. Local buckling ripples the flat walls with the corners staying put; distortional buckling rotates a flange and its lip about the web–flange corner.

Quick answers

What does 250S125-68 mean?

250S125-68 is an SSMA designation: 2-1/2 in stud or joist, 1-1/4 in flange, 68 mil (0.0713 in). The first number is the depth in hundredths of an inch, the letter is the style (S for a stud or joist with lips, T for track), the next number is the flange width in hundredths of an inch, and the last is the minimum thickness in mils. The design thickness is 0.0713 in.

What are the section properties of a 250S125-68 stud?

Area 0.346 in², weight 1.18 lb/ft, Ix 0.334 in⁴, Sx 0.268 in³, rx 0.984 in, Iy 0.058 in⁴, ry 0.408 in, J 0.586 ×10⁻³ in⁴, Cw 0.061 in⁶, computed by ColdCalc with rounded corners.

What is the allowable moment of a 250S125-68?

With the compression flange braced against lateral-torsional buckling and Fy = 50 ksi, AISI S100-24 gives a nominal strong-axis moment of 13.0 kip·in by the Direct Strength Method (governed by §F4): 7.8 kip·in allowable (ASD) or 11.7 kip·in design strength (LRFD). Unbraced lengths, holes and combined loads reduce it.

What are the local and distortional buckling loads of a 250S125-68?

By finite strip analysis, local buckling in compression occurs at 41.05 kip (half-wavelength 1.9 in) and distortional buckling at 28.55 kip (4.5 in), against a squash load Py of 17.28 kip.

Other 2-1/2 in studs

Computed by the ColdCalc engine from the SSMA dimensions (design thickness, lip length and bend radius as in the SSMA conventions), E = 29,500 ksi, with rounded corners. Manufacturers' published values can differ slightly in rounding and corner modelling; ColdCalc's effective section modulus is within 3 % of the SSMA tables for all 775 studs and tracks compared. Results must be reviewed by a qualified engineer. Validation