1400S350-118 stud properties and strength

SSMA 14 in stud or joist, 3-1/2 in flange, 118 mil (0.1242 in), Grade 50 (ASTM A1003 ST50H). Gross and effective properties, finite strip buckling loads and available strengths to AISI S100-24, computed by the ColdCalc engine.

The 1400S350-118 has an area of 2.742 in² and weighs 9.33 lb/ft. Its strong-axis moment of inertia is 75.201 in⁴ gross and 73.553 in⁴ effective at yield, and its effective section modulus is 10.363 in³. With the flange braced, its allowable moment is 278.9 kip·in (ASD), governed by distortional buckling (§F4).

14″3-1/2″1″ lipt = 0.1242″

Dimensions

Depth14in
Flange width3-1/2in
Lip length1in
Design thickness0.1242in
Minimum thickness0.1180in
Inside bend radius0.1863in
Yield stress Fy50ksi
Tensile strength Fu65ksi

Gross properties

Area A2.742in²
Weight9.33lb/ft
Ix75.201in⁴
Sx10.743in³
rx5.237in
Iy3.904in⁴
Sy1.464in³
ry1.193in

Torsion and effective section

J14.099×10⁻³ in⁴
Cw147.115in⁶
xo-2.116in
ro5.773in
β0.866
Ixe at yield73.553in⁴
Sxe10.363in³

Effective properties: AISI S100-24 Appendix 1, strong-axis bending with the extreme fiber at Fy.

Available strength (AISI S100-24)

ActionNominalASD, Rn/ΩLRFD, φRnGoverned by
Strong-axis moment, flange braced (DSM)465.77278.90419.19§F4 · kip·in
Strong-axis moment, flange braced (EWM)465.67278.84419.10§F4 · kip·in
Shear, web without holes24.9914.9622.49§G2.1 · kip
Axial, 8 ft tall, braced at 4 ft (DSM)66.4536.9156.48§E4 · kip
Axial, 9 ft tall, braced at 4 ft (DSM)66.4536.9156.48§E4 · kip
Axial, 10 ft tall, braced at 4 ft (DSM)66.4536.9156.48§E4 · kip
Axial, 12 ft tall, braced at 4 ft (DSM)66.4536.9156.48§E4 · kip
Axial, 14 ft tall, braced at 4 ft (DSM)66.4536.9156.48§E4 · kip
Axial, 16 ft tall, braced at 4 ft (DSM)66.4536.9156.48§E4 · kip

Axial: pinned ends, weak-axis and torsional bracing every 48 in, concentric load. No holes. Bending and axial load together, unbraced flanges, web crippling and deflection depend on the member: check them in the calculator.

Elastic buckling

0.00.51.01.52.0101001000half-wavelength, in (log scale)load factor (P/Py)Local0.25 at 10.6 inDistortional (by cFSM)0.37 at 34.4 in
Signature curve of the 1400S350-118 in pure compression: the elastic buckling load, as a multiple of the yield load Py, at each buckle half-wavelength. The marked points are the local (Pcrℓ) and distortional (Pcrd) buckling loads; the distortional mode has no distinct minimum here, so it was identified by its modal participation (cFSM). The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.
0.00.51.01.52.02.53.0101001000half-wavelength, in (log scale)load factor (M/My)Local1.36 at 7.7 inDistortional1.29 at 27.4 in
Signature curve of the 1400S350-118 in strong-axis bending: the elastic buckling load, as a multiple of the yield moment My, at each buckle half-wavelength. The marked points are the local (Mcrℓ) and distortional (Mcrd) buckling loads, each a minimum of the curve. The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.

Finite strip results

Py137.10kip
Pcrℓ at 10.634.03kip
Pcrd at 34.450.73kip
My537.15kip·in
Mcrℓ at 7.7730.47kip·in
Mcrd at 27.4695.36kip·in

Signature curve minima, labelled by modal participation (cFSM). Half-wavelengths in inches.

Local
34.03 kip at 10.6 in
Distortional
50.73 kip at 34.4 in
Buckled shapes of the 1400S350-118 in compression, from the same finite strip analysis. Local buckling ripples the flat walls with the corners staying put; distortional buckling rotates a flange and its lip about the web–flange corner.

Quick answers

What does 1400S350-118 mean?

1400S350-118 is an SSMA designation: 14 in stud or joist, 3-1/2 in flange, 118 mil (0.1242 in). The first number is the depth in hundredths of an inch, the letter is the style (S for a stud or joist with lips, T for track), the next number is the flange width in hundredths of an inch, and the last is the minimum thickness in mils. The design thickness is 0.1242 in.

What are the section properties of a 1400S350-118 stud?

Area 2.742 in², weight 9.33 lb/ft, Ix 75.201 in⁴, Sx 10.743 in³, rx 5.237 in, Iy 3.904 in⁴, ry 1.193 in, J 14.099 ×10⁻³ in⁴, Cw 147.115 in⁶, computed by ColdCalc with rounded corners.

What is the allowable moment of a 1400S350-118?

With the compression flange braced against lateral-torsional buckling and Fy = 50 ksi, AISI S100-24 gives a nominal strong-axis moment of 465.8 kip·in by the Direct Strength Method (governed by §F4): 278.9 kip·in allowable (ASD) or 419.2 kip·in design strength (LRFD). Unbraced lengths, holes and combined loads reduce it.

What are the local and distortional buckling loads of a 1400S350-118?

By finite strip analysis, local buckling in compression occurs at 34.03 kip (half-wavelength 10.6 in) and distortional buckling at 50.73 kip (34.4 in), against a squash load Py of 137.10 kip.

Other 14 in studs

Computed by the ColdCalc engine from the SSMA dimensions (design thickness, lip length and bend radius as in the SSMA conventions), E = 29,500 ksi, with rounded corners. Manufacturers' published values can differ slightly in rounding and corner modelling; ColdCalc's effective section modulus is within 3 % of the SSMA tables for all 775 studs and tracks compared. Results must be reviewed by a qualified engineer. Validation