1400S250-68 stud properties and strength

SSMA 14 in stud or joist, 2-1/2 in flange, 68 mil (0.0713 in), Grade 50 (ASTM A1003 ST50H). Gross and effective properties, finite strip buckling loads and available strengths to AISI S100-24, computed by the ColdCalc engine.

The 1400S250-68 has an area of 1.406 in² and weighs 4.78 lb/ft. Its strong-axis moment of inertia is 35.743 in⁴ gross and 29.039 in⁴ effective at yield, and its effective section modulus is 3.555 in³. With the flange braced, its allowable moment is 102.1 kip·in (ASD), governed by distortional buckling (§F4).

14″2-1/2″0.625″ lipt = 0.0713″

Dimensions

Depth14in
Flange width2-1/2in
Lip length0.625in
Design thickness0.0713in
Minimum thickness0.0677in
Inside bend radius0.1070in
Yield stress Fy50ksi
Tensile strength Fu65ksi

Gross properties

Area A1.406in²
Weight4.78lb/ft
Ix35.743in⁴
Sx5.106in³
rx5.042in
Iy0.865in⁴
Sy0.425in³
ry0.784in

Torsion and effective section

J2.383×10⁻³ in⁴
Cw32.653in⁶
xo-1.247in
ro5.253in
β0.944
Ixe at yield29.039in⁴
Sxe3.555in³

Effective properties: AISI S100-24 Appendix 1, strong-axis bending with the extreme fiber at Fy.

Available strength (AISI S100-24)

ActionNominalASD, Rn/ΩLRFD, φRnGoverned by
Strong-axis moment, flange braced (DSM)170.48102.09153.44§F4 · kip·in
Strong-axis moment, flange braced (EWM)170.42102.05153.38§F4 · kip·in
Shear, web without holes6.493.885.84§G2.1 · kip
Axial, 8 ft tall, braced at 4 ft (DSM)17.229.5714.63§E4 · kip
Axial, 9 ft tall, braced at 4 ft (DSM)17.229.5714.63§E4 · kip
Axial, 10 ft tall, braced at 4 ft (DSM)17.229.5714.63§E4 · kip
Axial, 12 ft tall, braced at 4 ft (DSM)17.229.5714.63§E4 · kip
Axial, 14 ft tall, braced at 4 ft (DSM)17.229.5714.63§E4 · kip
Axial, 16 ft tall, braced at 4 ft (DSM)17.229.5714.63§E4 · kip

Axial: pinned ends, weak-axis and torsional bracing every 48 in, concentric load. No holes. Bending and axial load together, unbraced flanges, web crippling and deflection depend on the member: check them in the calculator.

Elastic buckling

0.00.51.01.52.0101001000half-wavelength, in (log scale)load factor (P/Py)Local0.08 at 10.9 inDistortional (by cFSM)0.11 at 29.2 in
Signature curve of the 1400S250-68 in pure compression: the elastic buckling load, as a multiple of the yield load Py, at each buckle half-wavelength. The marked points are the local (Pcrℓ) and distortional (Pcrd) buckling loads; the distortional mode has no distinct minimum here, so it was identified by its modal participation (cFSM). The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.
0.00.51.01.52.0101001000half-wavelength, in (log scale)load factor (M/My)Local0.46 at 7.6 inDistortional (by cFSM)0.55 at 23.5 in
Signature curve of the 1400S250-68 in strong-axis bending: the elastic buckling load, as a multiple of the yield moment My, at each buckle half-wavelength. The marked points are the local (Mcrℓ) and distortional (Mcrd) buckling loads; the distortional mode has no distinct minimum here, so it was identified by its modal participation (cFSM). The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.

Finite strip results

Py70.30kip
Pcrℓ at 10.95.74kip
Pcrd at 29.27.66kip
My255.30kip·in
Mcrℓ at 7.6116.66kip·in
Mcrd at 23.5141.27kip·in

Signature curve minima, labelled by modal participation (cFSM). Half-wavelengths in inches.

Local
5.74 kip at 10.9 in
Distortional
7.66 kip at 29.2 in
Buckled shapes of the 1400S250-68 in compression, from the same finite strip analysis. Local buckling ripples the flat walls with the corners staying put; distortional buckling rotates a flange and its lip about the web–flange corner.

Quick answers

What does 1400S250-68 mean?

1400S250-68 is an SSMA designation: 14 in stud or joist, 2-1/2 in flange, 68 mil (0.0713 in). The first number is the depth in hundredths of an inch, the letter is the style (S for a stud or joist with lips, T for track), the next number is the flange width in hundredths of an inch, and the last is the minimum thickness in mils. The design thickness is 0.0713 in.

What are the section properties of a 1400S250-68 stud?

Area 1.406 in², weight 4.78 lb/ft, Ix 35.743 in⁴, Sx 5.106 in³, rx 5.042 in, Iy 0.865 in⁴, ry 0.784 in, J 2.383 ×10⁻³ in⁴, Cw 32.653 in⁶, computed by ColdCalc with rounded corners.

What is the allowable moment of a 1400S250-68?

With the compression flange braced against lateral-torsional buckling and Fy = 50 ksi, AISI S100-24 gives a nominal strong-axis moment of 170.5 kip·in by the Direct Strength Method (governed by §F4): 102.1 kip·in allowable (ASD) or 153.4 kip·in design strength (LRFD). Unbraced lengths, holes and combined loads reduce it.

What are the local and distortional buckling loads of a 1400S250-68?

By finite strip analysis, local buckling in compression occurs at 5.74 kip (half-wavelength 10.9 in) and distortional buckling at 7.66 kip (29.2 in), against a squash load Py of 70.30 kip.

Other 14 in studs

Computed by the ColdCalc engine from the SSMA dimensions (design thickness, lip length and bend radius as in the SSMA conventions), E = 29,500 ksi, with rounded corners. Manufacturers' published values can differ slightly in rounding and corner modelling; ColdCalc's effective section modulus is within 3 % of the SSMA tables for all 775 studs and tracks compared. Results must be reviewed by a qualified engineer. Validation