1400S300-118 stud properties and strength

SSMA 14 in stud or joist, 3 in flange, 118 mil (0.1242 in), Grade 50 (ASTM A1003 ST50H). Gross and effective properties, finite strip buckling loads and available strengths to AISI S100-24, computed by the ColdCalc engine.

The 1400S300-118 has an area of 2.525 in² and weighs 8.59 lb/ft. Its strong-axis moment of inertia is 65.656 in⁴ gross and 61.981 in⁴ effective at yield, and its effective section modulus is 8.429 in³. With the flange braced, its allowable moment is 235.8 kip·in (ASD), governed by distortional buckling (§F4).

14″3″0.625″ lipt = 0.1242″

Dimensions

Depth14in
Flange width3in
Lip length0.625in
Design thickness0.1242in
Minimum thickness0.1180in
Inside bend radius0.1863in
Yield stress Fy50ksi
Tensile strength Fu65ksi

Gross properties

Area A2.525in²
Weight8.59lb/ft
Ix65.656in⁴
Sx9.379in³
rx5.100in
Iy2.175in⁴
Sy0.906in³
ry0.928in

Torsion and effective section

J12.981×10⁻³ in⁴
Cw79.537in⁶
xo-1.525in
ro5.403in
β0.920
Ixe at yield61.981in⁴
Sxe8.429in³

Effective properties: AISI S100-24 Appendix 1, strong-axis bending with the extreme fiber at Fy.

Available strength (AISI S100-24)

ActionNominalASD, Rn/ΩLRFD, φRnGoverned by
Strong-axis moment, flange braced (DSM)393.80235.81354.42§F4 · kip·in
Strong-axis moment, flange braced (EWM)393.66235.72354.29§F4 · kip·in
Shear, web without holes24.9914.9622.49§G2.1 · kip
Axial, 8 ft tall, braced at 4 ft (DSM)51.1728.4343.50§E4 · kip
Axial, 9 ft tall, braced at 4 ft (DSM)51.1728.4343.50§E4 · kip
Axial, 10 ft tall, braced at 4 ft (DSM)51.1728.4343.50§E4 · kip
Axial, 12 ft tall, braced at 4 ft (DSM)51.1728.4343.50§E4 · kip
Axial, 14 ft tall, braced at 4 ft (DSM)51.1728.4343.50§E4 · kip
Axial, 16 ft tall, braced at 4 ft (DSM)51.1728.4343.50§E4 · kip

Axial: pinned ends, weak-axis and torsional bracing every 48 in, concentric load. No holes. Bending and axial load together, unbraced flanges, web crippling and deflection depend on the member: check them in the calculator.

Elastic buckling

0.00.51.01.52.0101001000half-wavelength, in (log scale)load factor (P/Py)Local0.23 at 13.5 inDistortional (by cFSM)0.27 at 25.2 in
Signature curve of the 1400S300-118 in pure compression: the elastic buckling load, as a multiple of the yield load Py, at each buckle half-wavelength. The marked points are the local (Pcrℓ) and distortional (Pcrd) buckling loads; the distortional mode has no distinct minimum here, so it was identified by its modal participation (cFSM). The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.
0.00.51.01.52.02.53.0101001000half-wavelength, in (log scale)load factor (M/My)Local (by cFSM)1.34 at 7.3 inDistortional1.08 at 17.3 in
Signature curve of the 1400S300-118 in strong-axis bending: the elastic buckling load, as a multiple of the yield moment My, at each buckle half-wavelength. The marked points are the local (Mcrℓ) and distortional (Mcrd) buckling loads; the distortional mode has no distinct minimum here, so it was identified by its modal participation (cFSM). The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.

Finite strip results

Py126.23kip
Pcrℓ at 13.529.40kip
Pcrd at 25.233.61kip
My468.97kip·in
Mcrℓ at 7.3627.36kip·in
Mcrd at 17.3508.04kip·in

Signature curve minima, labelled by modal participation (cFSM). Half-wavelengths in inches.

Local
29.40 kip at 13.5 in
Distortional
33.61 kip at 25.2 in
Buckled shapes of the 1400S300-118 in compression, from the same finite strip analysis. Local buckling ripples the flat walls with the corners staying put; distortional buckling rotates a flange and its lip about the web–flange corner.

Quick answers

What does 1400S300-118 mean?

1400S300-118 is an SSMA designation: 14 in stud or joist, 3 in flange, 118 mil (0.1242 in). The first number is the depth in hundredths of an inch, the letter is the style (S for a stud or joist with lips, T for track), the next number is the flange width in hundredths of an inch, and the last is the minimum thickness in mils. The design thickness is 0.1242 in.

What are the section properties of a 1400S300-118 stud?

Area 2.525 in², weight 8.59 lb/ft, Ix 65.656 in⁴, Sx 9.379 in³, rx 5.100 in, Iy 2.175 in⁴, ry 0.928 in, J 12.981 ×10⁻³ in⁴, Cw 79.537 in⁶, computed by ColdCalc with rounded corners.

What is the allowable moment of a 1400S300-118?

With the compression flange braced against lateral-torsional buckling and Fy = 50 ksi, AISI S100-24 gives a nominal strong-axis moment of 393.8 kip·in by the Direct Strength Method (governed by §F4): 235.8 kip·in allowable (ASD) or 354.4 kip·in design strength (LRFD). Unbraced lengths, holes and combined loads reduce it.

What are the local and distortional buckling loads of a 1400S300-118?

By finite strip analysis, local buckling in compression occurs at 29.40 kip (half-wavelength 13.5 in) and distortional buckling at 33.61 kip (25.2 in), against a squash load Py of 126.23 kip.

Other 14 in studs

Computed by the ColdCalc engine from the SSMA dimensions (design thickness, lip length and bend radius as in the SSMA conventions), E = 29,500 ksi, with rounded corners. Manufacturers' published values can differ slightly in rounding and corner modelling; ColdCalc's effective section modulus is within 3 % of the SSMA tables for all 775 studs and tracks compared. Results must be reviewed by a qualified engineer. Validation