FundamentalsBeginner12 min read

Cold-formed steel design: a practical guide to AISI S100-24

How cold-formed steel studs, joists, columns and purlins are designed to AISI S100-24: buckling modes, DSM and EWM, load combinations, the checks that govern, and where to start.

By ColdCalc Engineering
In short
  • Cold-formed steel is sheet steel bent to shape at room temperature: C-studs, joists, tracks, Z- and C-purlins and girts. Framing members are typically 0.018 to 0.12 in thick, and in the US, Mexico and Canada they are designed to AISI S100-24, now published by the Steel Deck Institute (SDI).
  • The walls are so thin that they buckle before the steel yields. Every member check comes down to three buckling modes: local, distortional and global. The member's strength is the lowest of the three.
  • Strength is computed with the Effective Width Method (Appendix 1) or the Direct Strength Method (§E3.2, §E4, §F3.2, §F4), using ASD or LRFD in the US and Mexico and LSD in Canada. Load combinations come from ASCE 7 (§B2).
  • Each member type has its own governing checks: wall studs are governed by axial load plus bending (§H1.2) with P-δ, joists by bending, shear, web crippling and deflection, columns by §E2 to §E4, and lapped purlins by §I6.2.1 or §H4.
  • For ColdCalc's starting wall stud, a 600S162-54 at 12 ft, the governing check is axial load plus bending, at a ratio of 0.31.

This guide is for engineers who know steel design but are new to cold-formed steel: what makes thin steel different, how AISI S100-24 is organized, and which checks govern studs, joists, columns and purlins. Each topic links to an article that goes deeper.

What cold-formed steel is, and where it is used#

Cold-formed steel members are made by bending flat steel sheet, strip or plate at room temperature, usually by roll-forming. The Specification covers members cold-formed from steel up to 1 in thick (§A1.1), but most framing is far thinner: the SSMA sizes in ColdCalc's catalog run from 18 mil (0.018 in) to 118 mil (0.118 in).

The common members are:

  • Studs: vertical C-sections in walls, carrying gravity load from above, wind across the wall, or both.
  • Joists and rafters: horizontal C-sections carrying floor or roof load in bending.
  • Tracks: unlipped channels at the top and bottom of walls that hold the studs, and rims at the ends of joists.
  • Purlins and girts: Z- and C-sections spanning between the frames of metal buildings and supporting the roof and wall panels. Z-purlins are often lapped over the supports to make them continuous.

Studs, joists and tracks are named with SSMA designations such as 600S162-54. The SSMA designation guide explains how to read them.

Why it is designed differently from hot-rolled steel#

A W-shape has flanges and webs thick enough that, for most members, the design question is when the steel yields or the member buckles as a whole. A cold-formed stud's web can be more than 100 times as wide as it is thick. Plates that slender buckle at a fraction of the yield stress.

Take the 600S162-54 stud. Its squash load, area times yield stress, is 27.82 kip, but its web buckles locally at a local buckling load of only 7.81 kip. The stud does not fail there: thin plates carry load well past their buckling load. But the strength equations have to account for that buckling, and that is the main thing AISI S100 does that AISC 360 rarely needs to.

Two other differences follow from the shapes:

  • Open, singly-symmetric sections. A C-section's shear center is outside its web, so loads through the web twist it, and flexural-torsional buckling often governs columns.
  • Thin webs crush at supports. Web crippling (§G5) is a routine check for joists and purlins.

The Specification: AISI S100-24#

The design standard is the North American Specification for the Design of Cold-Formed Steel Structural Members, 2024 Edition: ANSI/SDI AISI S100-2024, called S100-24. The Steel Deck Institute took over AISI's cold-formed steel standards in 2023 and published S100-24, a revision of S100-16(2020) with Supplement 3 (S3-22). It is a free download from sdi.org. It applies in the United States, Mexico and Canada, with country-specific provisions in Appendices A and B (§A1.2.1).

ChapterCovers
A, BScope, materials, loads, design basis, dimensional limits
CStability: second-order analysis and bracing
DTension
ECompression
FFlexure
GShear, web crippling and torsion
HCombined forces
IAssemblies and systems: built-up members, diaphragms, purlin roofs, racks
JConnections: welds, bolts, screws
K, L, MTests and special cases, serviceability, fatigue
Appendix 1Effective widths of elements
Appendix 2Elastic buckling analysis of members

Your building code decides which edition applies. The 2024 International Building Code references S100-16(2020) with S2-20; S100-24 is expected to be adopted in the 2027 International Codes. For light-frame construction, the user note to §I4 points to the companion AISI standards S220, S240 and S400. The S100-24 changes article lists what is new.

ASD, LRFD and LSD#

Every limit state in S100-24 gives a nominal strength Rn. The design method turns it into an available strength:

  • ASD (§B3.2.1): Rn/Ω ≥ the required strength from ASD load combinations.
  • LRFD (§B3.2.2): φRn ≥ the required strength from LRFD load combinations.
  • LSD (§B3.2.3): the Canadian limit states design, with its own φ, used with the National Building Code of Canada.

ASD and LRFD apply in the United States and Mexico, LSD in Canada (§A1.2.3). The factors depend on the limit state:

Limit stateΩ (ASD)φ (LRFD)φ (LSD)
Compression, §E2 to §E41.800.850.80
Bending, §F2 to §F41.670.900.90
Shear, §G21.670.900.75

Use one method throughout a check, with the load combinations written for it.

The three buckling modes#

Thin-walled members buckle in three ways, each with its own buckle length:

  • Local buckling: the flat walls ripple in short waves about as long as the plates are wide, while the corners stay straight. Its post-buckling reserve is large.
  • Distortional buckling: a lipped flange rotates about the web–flange corner, and the cross-section changes shape. The waves are several times longer and the reserve is smaller.
  • Global buckling: the member bends, twists or both between its braces, like any column or beam.
Local
7.81 kip at 4.5 in
Distortional
12.72 kip at 16.4 in
Buckled shapes of the 600S162-54 in compression, from the same finite strip analysis. Local buckling ripples the flat walls with the corners staying put; distortional buckling rotates a flange and its lip about the web–flange corner.

AISI S100-24 checks each mode: global buckling in §E2 and §F2, local buckling interacting with global buckling in §E3 and §F3, and distortional buckling in §E4 and §F4. The available strength is the smallest (§E1, §F1). The buckling modes article shows how a finite strip signature curve separates them, and the finite strip article explains the analysis.

Two ways to compute strength: EWM and DSM#

The Specification offers two methods for local and distortional buckling:

  • The Effective Width Method (EWM), Appendix 1, treats each flat plate separately. A plate under stress f keeps an effective width b = ρw (Eq. 1.1-1), where ρ = (1 − 0.22/λ)/λ for λ > 0.673 (Eq. 1.1-2) and λ = √(f/Fcr). The member's strength uses the properties of the effective section.
  • The Direct Strength Method (DSM) uses elastic buckling loads of the whole cross-section, from a finite strip analysis (Appendix 2 §2.2) or closed-form expressions (§2.3). For local buckling of a column, S100-24 gives:
Pnℓ = 1.2 Pne (1 + 0.10λℓ2) / (1 + 0.55λℓ2) ≤ Pne, with λℓ = √(Pne/Pcrℓ)
Eq. E3.2-1

This is a new form: S100-24 replaced the S100-16 DSM equations. Both are permitted within the limits of Table B4.1-1. In bending with the compression flange braced, distortional buckling governs these four studs by either method, and §F4 is the same in both, so the strengths match:

SectionEWM MnDSM MnDSM / EWMDSM governs by
362S162-339.09.01.00Distortional (F4)
600S162-5442.242.21.00Distortional (F4)
800S200-5466.866.81.00Distortional (F4)
1000S250-68122.3122.41.00Distortional (F4)

kip·in

Nominal strong-axis bending strength with the compression flange braced (no lateral-torsional buckling), AISI S100-24. EWM: Sections F3.1 (Appendix 1) and F4. DSM: Sections F3.2 and F4, with finite strip buckling values. Computed by ColdCalc.

Local buckling is where the methods part. EWM vs DSM shows where the two diverge, and the Direct Strength Method article works through a column step by step.

Load combinations from ASCE 7#

Section B2 sends you to the applicable building code for loads and combinations, and to ASCE/SEI 7 in the US and Mexico where no code is stipulated. ColdCalc generates the basic combinations of ASCE 7-22 §2.3.1 (LRFD) or §2.4.1 (ASD), or the 7-16 versions; it does not generate seismic combinations. For LRFD under ASCE 7-22 they are:

  1. 1.4D
  2. 1.2D + 1.6L + 0.5(Lr or 0.3S or R)
  3. 1.2D + 1.6Lr (or 1.0S, or 1.6R) + (L or 0.5W)
  4. 1.2D + 1.0W + L + 0.5(Lr or 0.3S or R)
  5. 0.9D + 1.0W

(ASCE 7-22 snow loads are strength-level, hence 1.0S and 0.3S.) Two cases matter more for light framing than for heavy: wind acts both ways, so pressure and suction put opposite flanges in compression, and 0.9D + 1.0W governs uplift on light roofs, with the purlin's unbraced flange in compression. Deflection uses service combinations, with 0.42W on components and cladding as IBC Table 1604.3 permits.

The checks by member type#

ColdCalc analyzes each member under every combination and makes each check at every location that could govern.

Wall studs

A wind-bearing stud carries axial load from above and wind across the wall. The checks are:

  • Axial strength (§E2 to §E4), with the strong-axis length the stud height and the weak-axis and torsional lengths the bridging spacing.
  • Bending strength (§F2 to §F4), including lateral-torsional buckling between bridging lines when the compression flange is unbraced.
  • Axial load plus bending, Eq. H1.2-1: P/Pa + Mx/Max + My/May ≤ 1.0, with the moment amplified for P-δ by the amplifier B1 = Cm/(1 − αP/Pe1) (Eq. C1.2.1.1-3).
  • Shear (§G2) at the supports, and bending plus shear (Eq. H2-1).
  • Deflection under service wind, commonly L/240 for walls with brittle finishes.

Here are all of them for ColdCalc's starting stud: a 600S162-54, 12 ft tall at 16 in on center, bridged every 48 in.

CheckClauseDemandCapacityRatio
Axial compression
0.00 ft, 1.2D + 1.6L
§E2, §E3.2, §E41.44 kip9.50 kip0.15
Bending, strong axis
6.00 ft, 1.2D + W (Wind suction) + L
§F2.2, §F3.2, §F47.40 kip·in37.71 kip·in0.20
Shear
0.00 ft, 1.2D + W (Wind pressure) + L
§G2.10.20 kip4.71 kip0.04
Axial and bending combined
6.00 ft, 1.2D + W (Wind suction) + L
§H1.2, Eq. H1.2-1––0.31
Bending and shear combined
6.00 ft, 1.2D + W (Wind suction) + L
§H2, Eq. H2-1––0.18
Deflection
6.00 ft, 0.42W (Wind pressure)
L/240, service0.077 in0.600 in0.13
The checks of a 600S162-54 wall stud, 12 ft tall at 16 in on center, bridged every 48 in, with axial dead and live load and 25 psf wind, AISI S100-24 LRFD with ASCE 7-22 combinations. Each ratio is the worst over every location and combination (8 strength and 2 service combinations). Computed by ColdCalc.

At mid-height under wind suction the axial load is 1.08 kip, the P-δ amplifier is B1 = 1.028, and the amplified moment is 7.40 kip·in. The interaction sums P/Pa = 0.11 and Mx/Max = 0.20. The wall stud design example goes through every number.

Joists

A floor joist is a beam whose top flange is usually held by the deck. Its checks are:

  • Bending (§F2 to §F4). With the compression flange braced by the deck there is no lateral-torsional buckling, but local and distortional buckling remain. Where the bottom flange is in compression, over an interior support or under uplift, lateral-torsional buckling comes back.
  • Shear (§G2): Vn = 1.2Vy/(1 + 0.57λv2) ≤ Vy (Eq. G2.1-1), with holes in the web per §G3.
  • Bending plus shear (Eq. H2-1), important over interior supports of continuous joists.
  • Web crippling at supports and concentrated loads (§G5), and bending plus web crippling (§H3) at interior supports. If the web cannot take the reaction, add a bearing stiffener (§G7).
  • Deflection, commonly L/360 under live load and L/240 under total load for floors.

The web crippling article covers the four load cases and Eq. G5-1.

Columns

An axially loaded member's strength is the smallest of three (§E1):

  • §E2, yielding and global buckling: Pne = AgFn, with Fn from λc = √(Fy/Fcre) (Eqs. E2-1 to E2-4). Fcre is the lowest of flexural, torsional and flexural-torsional buckling (Appendix 2 §2.3.1.1), so each axis needs its own effective length.
  • §E3, local buckling interacting with global buckling: EWM (§E3.1) or DSM (Eq. E3.2-1).
  • §E4, distortional buckling: Pnd from λd = √(Py/Pcrd) (Eqs. E4-1 and E4-2).

For the starting stud as a column, global buckling gives Pne = 16.70 kip, local buckling Pnℓ = 11.17 kip and distortional buckling Pnd = 15.02 kip. Local buckling governs, and the LRFD design strength is φPnℓ = 9.50 kip.

Purlins and girts

Lapped Z-purlins are continuous beams with laps over the supports, a through-fastened roof on the top flange, and loads that do not pass through the shear center. Their governing checks are:

  • Gravity: bending with the top flange braced by the panels, and lateral-torsional buckling of the bottom flange near the supports, where it is in compression. Web crippling and §H3 at the supports.
  • Uplift with through-fastened panels: §I6.2.1 gives Mn = R·Mno (Eq. I6.2.1-1), with the R factor from Table I6.2.1-1 (0.70 for continuous Z-sections, 0.40 to 0.70 for simple spans by depth and profile) within the limits that section lists. Distortional buckling is excluded when §I6.2.1 is used.
  • Bending plus torsion: where the purlin twists, §H4 adds the warping stress from the bimoment: Mx/Max + My/May + B/Ba ≤ 1.0 (Eq. H4-1). §H4 does not apply where §I6.2.1 or §I6.2.2 is used.

The Z-purlin article covers laps, anti-roll bracing and the R factor.

Bracing: bridging, sheathing and blocking#

Three kinds of bracing are common, and each is part of the design:

  • Bridging runs through the stud or joist webs at intervals, typically every 4 ft in walls. It sets the weak-axis and torsional unbraced lengths and stops twist. Brace forces accumulate along a wall, so the bridging and its anchorage need their own design. For one concentrically loaded column, §C2.3.1 requires a brace strength of 1 % of the axial load (Eq. C2.3.1-1).
  • Sheathing screwed to a flange stops that flange moving sideways. Where both flanges of a beam are connected to deck or sheathing that restrains them, §C2.2 requires no further bracing. Sheathing on one face only braces one flange, so under wind suction the other flange relies on the bridging.
  • Blocking at supports keeps joists and purlins from rolling. §B3.4 requires beams to be restrained against rotation about their longitudinal axis at their supports.

For purlin roofs, §I6.4 covers the anchorage of the bracing forces.

A step-by-step workflow#

    1. Define the member: spans, supports, laps, and where the bracing is. Decide which flange the sheathing or deck holds.
    2. List the loads by source (dead, live, roof, snow, wind) and build the ASCE 7 combinations for ASD or LRFD, plus service combinations for deflection.
    3. Pick a trial section by its SSMA designation, and confirm the grade and design thickness.
    4. Analyze the member for every combination: axial force, moments, shear, torsion, reactions and deflections. Amplify moments in compression members for P-δ.
    5. Find the elastic buckling values (Pcrℓ, Pcrd, Mcrℓ, Mcrd, Fcre) by finite strip analysis or Appendix 2.
    6. Compute the strengths: Chapters E, F and G, by DSM or EWM.
    7. Check the interactions of Chapter H at every location, under every combination.
    8. Check deflection under service loads with the effective moment of inertia (Chapter L).
    9. Design the bracing and connections (Chapters C and J), then iterate on the section.

Common mistakes#

  • Designing with the mils. 54 mil is the minimum thickness; the design thickness is 0.0566 in.
  • Forgetting distortional buckling. A joist fully braced by a deck has no lateral-torsional buckling, but distortional buckling (§F4) is still checked.
  • Assuming sheathing braces both flanges. One-sided sheathing leaves the other flange free when wind reverses.
  • Skipping web crippling at supports and point loads.
  • Leaving out P-δ in studs with axial load.
  • Using S100-16 DSM equations under S100-24. The local and distortional equations changed.
  • Ignoring web holes. Punchouts reduce shear, web crippling and buckling strengths (§G3, §G6, and net-section DSM terms).

Where to go next#

Every SSMA stud and track has a page of properties and strengths under /sections, the glossary defines every symbol, and the comparison sets ColdCalc beside CFS and CUFSM.

What code is used to design cold-formed steel?

In the United States, Mexico and Canada, cold-formed steel members are designed to the North American Specification, AISI S100. The current edition is ANSI/SDI AISI S100-2024 (S100-24), published by the Steel Deck Institute. The 2024 IBC references S100-16(2020) with S2-20, so check which edition your building code adopts.

Why is cold-formed steel designed differently from hot-rolled steel?

Cold-formed members are so thin that their flat walls buckle locally, often below the yield stress, and lipped flanges can buckle distortionally. AISI S100 accounts for local, distortional and global buckling in every member check, while hot-rolled design under AISC 360 is mostly governed by yielding and global buckling.

What is the difference between the Effective Width Method and the Direct Strength Method?

The Effective Width Method reduces each buckled plate to an effective width and computes strength from the effective section. The Direct Strength Method uses the elastic buckling loads of the whole cross-section, usually from a finite strip analysis, in strength equations for local and distortional buckling. Both are permitted by AISI S100-24 within the limits of Table B4.1-1.

What checks are required for a cold-formed steel wall stud?

A wind-bearing stud is checked for axial strength (Sections E2 to E4), bending strength (F2 to F4), combined axial load and bending (Eq. H1.2-1) with the P-delta amplifier B1, shear (G2), combined bending and shear (Eq. H2-1), and deflection under service wind. The bridging spacing sets the weak-axis and torsional buckling lengths.

How thick is light gauge steel framing?

SSMA framing is designated by its minimum steel thickness in mils (thousandths of an inch), from 18 mil (0.018 in) to 118 mil (0.118 in) in the common range. The design thickness used in calculations is the minimum divided by 0.95, for example 0.0566 in for 54 mil.