Design examplesAdvanced12 min read

Designing lapped Z-purlins: laps, anti-roll bracing and the R factor

How continuous lapped Z-purlins carry load, where they are checked, what anti-roll bracing does, and how the I6.2.1 R factor sets uplift strength for through-fastened roofs.

By ColdCalc Engineering
In short
  • Lapped Z-purlins are nested and bolted over each interior support. Inside the lap two members carry the moment, so the critical sections move: to the lap ends and the unbraced bottom flange near the supports under gravity, to mid-span under uplift, and to the support itself for web crippling with bending (§H3).
  • A Z has a nonzero product of inertia, so vertical load pushes it sideways as well as down. The roof panel and the anchorage required by §I6.4 hold it. Loads applied on the top flange, away from the shear center, also twist it, and §H4 checks bending together with the warping bimoment.
  • Under uplift the panel-fastened flange is in tension and the free flange in compression. AISI S100-24 §I6.2.1 gives Mn = R·Mno, with R = 0.70 for continuous Z-sections (Table I6.2.1-1). It applies only within limits (a) to (o), and not between the inflection points next to a support.
  • In ColdCalc's purlin example (an 8 in Z, two 25 ft spans, 2 ft laps), strong-axis bending governs at a ratio of 0.97, at the end of the lap, 24 in past the interior support, under 1.2D + S.

Purlins look simple, but they are among the harder members in cold-formed design. The section is unsymmetric, the load acts on a flange rather than through the shear center, one flange is held by the roof panel and the other is free, and the laps make the system continuous. This article takes each effect in turn, with the S100-24 provisions and a two-span example computed by ColdCalc.

How a lapped Z-purlin system works#

Z-sections nest: turn one end for end and its flanges fit inside the next. Adjacent purlins overlap a set distance into each span over the support and are bolted through the webs, so the line acts as a continuous beam. That has two advantages over simple spans:

  • Smaller moments. Continuity moves moment from mid-span to the supports. For two equal spans under uniform load, the support moment is wL²/8 and the largest span moment is about 0.07wL², against wL²/8 at mid-span of a simple beam.
  • A double section where the moment is largest. Inside the lap there are two members, so both the stiffness and the strength double exactly where the negative moment peaks. The moment a single member must resist is the one at the end of the lap, which is smaller.

Because the lap is stiffer than the rest of the span, it attracts moment. A prismatic two-span beam under uniform load has its inflection point 0.25L from the interior support; in the example below the lap pushes it out to 0.28L, or 6.9 ft from the support.

That leaves four critical regions in every span: the lap ends, where one member takes the full negative moment; the stretch from the support to the next brace, where the bottom flange is in compression and unbraced; mid-span, where the positive moment peaks; and the support, for web crippling together with the moment.

-150-125-100-75-50-25025507510005101520253035404550position, ftMx, kip·ingovernstop flange in compressionbottom flange in compression
Strong-axis moment along the two-span purlin: the governing gravity combination (1.2D + S, solid) and the uplift combination that governs the R-factor check (0.9D + W (Wind uplift), dashed). Positive moment puts the top flange, which the roof panel braces, in compression. The shaded bands are the laps; triangles are the supports, ticks the mid-span braces, and the dot is where the governing check occurs. Inside a lap the diagram is the total moment, which the two members share. Computed by ColdCalc.

Under the governing gravity combination the total moment over the interior support is 125.7 kip·in. The two members in the lap share it equally, because they are identical, so each carries 62.9 kip·in. At the lap end the moment has fallen to 82.1 kip·in, but one member now carries all of it. That is why the lap end, not the support, is the critical bending section.

The worked example#

The example is the starting design of ColdCalc's Purlin or girt member type:

InputValue
SectionZ 8 × 2.5 in, 0.9 in lips, 0.085 in thick; Fy = 55 ksi, Fu = 70 ksi
SpansTwo spans of 25 ft, pinned at three rafters, 3 in bearing
Laps24 in into each span at the interior support
Spacing and slope5 ft on center, roof slope 9.46° (2:12)
LoadsDead 3 psf plus self weight, snow 20 psf, wind uplift 20 psf, applied on the top flange over the web
BracingThrough-fastened panel on the top flange; anti-roll braces at mid-span stop sideways movement and twist
DesignLRFD, ASCE 7-22 combinations, Direct Strength Method with finite strip buckling, R = 0.7 for uplift

ColdCalc generates the ASCE 7-22 combinations (snow takes a load factor of 1.0), analyzes the purlin under each, and checks every S100-24 provision at every support, brace, lap end and peak:

CheckS100-24Where, and combinationRatio
Bending, strong axisgoverns§F2.2, §F3.2, §F4at the end of the lap, 24 in past the interior support; 1.2D + S0.97
Shear§G2.1at the end of the lap, 24 in before the interior support; 1.2D + S0.15
Shear along the flanges§G2.1at the end of the lap, 24 in before the interior support; 1.2D + S0.04
Web crippling§G5, EOFat an end support; 1.2D + S0.39
Bending and shear combined§H2, Eq. H2-1at the end of the lap, 24 in past the interior support; 1.2D + S0.63
Bending and web crippling combined§H3, Eq. H3-3 (nested Z)over the interior support; 1.2D + S0.47
Bending and torsion combined§H4, Eq. H4-1 (limit 1.25)at the end of the lap, 24 in past the interior support; 1.2D + S0.97
DeflectionL/240, service10.0 ft from an end support; D + 0.7S0.67
Every check ColdCalc runs on the purlin, with the largest ratio of each over all LRFD combinations and all checked points. For an interaction (H2, H3, H4) the ratio is the equation's value over its limit, or the largest single term when that is higher. Computed by ColdCalc to AISI S100-24.

The sections below explain each row.

Biaxial bending and the product of inertia#

A Z-section is point-symmetric, not symmetric about either axis. Its product of inertia Ixy is not zero, so its principal axes are inclined to the web. For this purlin Ix = 11.37 in⁴, Iy = 1.57 in⁴ and Ixy = 3.08 in⁴, and the major principal axis is turned 16.1° from the x axis.

Load a free Z vertically and it bends about both principal axes at once. It deflects down and sideways, and the sideways movement is large. For this section an unrestrained Z would deflect 2.13 times as far down as a Z held laterally, and sideways by 1.96 times its downward deflection. (Those are IxIy/(IxIy − Ixy²) and Ixy/Iy.)

In a roof, the panel on the top flange stops that sideways movement. The purlin then bends about its geometric x axis, the bending stress is simply Mx·y/Ix, and the Chapter F strengths apply. The force the panel supplies to hold the purlin straight accumulates along the roof, and the anchorage of §I6.4 has to carry it (see anti-roll bracing).

ColdCalc's analysis keeps Ixy and couples the two directions. Its design moments are the curvature moments E·Ix·v″ and E·Iy·u″, so a laterally restrained Z has My = 0 for the checks, and the Ixy/Ix·Mx a statical analysis would show goes into the restraint.

Torsion from loads off the shear center#

A Z's shear center is at its centroid, at mid-depth of the web, and roof load arrives at the top flange. On a flat roof, vertical load over the web passes through the shear center and causes no torque. On a sloped roof the down-slope component acts parallel to the flanges, half the depth above the shear center, and twists the section. A C is worse: its shear center is outside the web, so even vertical load twists it.

A thin-walled open section resists twist partly by St. Venant shear and partly by warping. Restrained warping produces longitudinal stresses, measured by the bimoment B. ColdCalc computes the bimoment with a Vlasov warping torsion analysis between the twist restraints (supports and braces), and §H4 combines it with bending:

Mx/Max + My/May + B/Ba ≤ 1.0
Eq. H4-1

Each ratio must also not exceed 1.0 on its own. Ba comes from §G8.1, where Bn = By = FyCw/ωn,max (Eq. G8.1-2), with an optional inelastic reserve. Two details of §H4 matter for purlins:

  • The 1.25 limit. For Z-sections where the bimoment causes tension at the free edges of the flanges, the right-hand side may be increased to 1.25. ColdCalc checks the sign of the warping stress at the lip tips and applies 1.25 only then.
  • Not with the R factor. §H4 "shall not apply if the provisions of Section I6.2.1 or I6.2.2 are used". The Commentary explains why: the R factors come from tests in which torsion was already present.

In the example the braces at mid-span and the supports restrain twist, so the bimoment stays small: at the governing point B/Ba = 0.029, against Mx/Max = 0.97. The sum, 0.996, is within the limit of 1.25, so the H4 ratio is set by the bending term alone.

Gravity: lap ends and the unbraced bottom flange#

Under gravity the positive moment at mid-span puts the top flange in compression. The panel braces that flange, so lateral-torsional buckling cannot occur there, and the strength is the local (§F3) and distortional (§F4) values of a braced section. Here the largest positive moment, 59.5 kip·in, is well within that strength.

Near the interior support the moment is negative and the bottom flange is in compression. The panel on the top flange does not brace it. Between the support and the mid-span brace, a length of 12.5 ft, the purlin can buckle laterally and torsionally. For a point-symmetric Z, Appendix 2 gives

Mcre = Cb·ro·√(Pey·Pt) / 2
Eq. 2.3.1.2.3-1

where ro is the polar radius of gyration about the shear center, Pey the weak-axis flexural buckling load and Pt the torsional buckling load over the unbraced length. Cb (Eq. 2.3.1-8) rewards the steep moment gradient between the support and the brace: here Cb = 2.56, and Mcre = 94.4 kip·in. S100-24 §F2.2 turns it into the global strength, with the plastic moment Mp = 185.4 kip·in:

Mne = Mp(1 − 0.25Mp/Mcre) = 185.4(1 − 0.25 × 185.4/94.4) = 94.4 kip·in
Eq. F2.2-1

Local buckling (§F3.2, 97.0 kip·in) and distortional buckling (§F4, 140.3 kip·in) are higher, so lateral-torsional buckling governs: φMn = 0.90 × Mne = 84.9 kip·in against Mu = 82.1 kip·in at the lap end.

Inflection points are not braces

A common simplification treats the inflection point as a brace for the bottom flange, which shortens the unbraced length considerably. The User Note to Appendix 2 §2.3.1 says otherwise: "locations of zero moment (inflection points) are not considered restraint locations". ColdCalc follows the Specification by default and offers the assumption as a labelled option, as CFS does. The table in Lap modelling choices shows its effect.

Uplift and the R factor (§I6.2.1)#

Under uplift the moments reverse: at mid-span the panel-fastened top flange is in tension and the free bottom flange in compression. The screws restrain the purlin only partly, so, as the Commentary puts it, the strength lies between that of a fully braced member and an unbraced one. §I6.2.1 captures it with a test-based reduction:

Mn = R·Mno
Eq. I6.2.1-1

with Ωb = 1.67 (ASD) and φb = 0.90 (LRFD). Mno is the local buckling strength from §F3 with Fn = Fy or Mne = My, and distortional buckling (§F4) is excluded. R comes from Table I6.2.1-1:

SpanMember depth dProfileR
Simpled ≤ 6.5 inC or Z0.70
Simple6.5 in < d ≤ 8.5 inC or Z0.65
Simple8.5 in < d ≤ 12 inZ0.50
Simple8.5 in < d ≤ 12 inC0.40
ContinuousAny, within condition (a)C0.60
ContinuousAny, within condition (a)Z0.70

R may be used only for roof and wall systems that meet the conditions of §I6.2.1. Outside them, the Specification calls for full-scale tests (§K2.1) or a rational engineering analysis.

  • Member: (a) depth ≤ 12 in; (b) flanges with edge stiffeners; (c) 60 ≤ depth/thickness ≤ 170; (d) 2.8 ≤ depth/flange width ≤ 5.5; (e) flange width ≥ 2.125 in; (f) 16 ≤ flat width/thickness of the flange ≤ 43.
  • System: (g) for continuous spans, laps of at least 1.5d from the center of the support in each direction; (h) spans no longer than 33 ft; (i) both flanges held laterally at the supports.
  • Panel and fasteners: (j) steel panels of at least 50 ksi yield and 0.018 in base metal thickness, with ribs at least 1-1/8 in deep at no more than 12 in on center; (k) glass fiber blanket insulation 0 to 6 in thick; (l) at least No. 12 self-drilling or self-tapping screws or 3/16 in rivets, with 1/2 in washers; (m) no standoff screws; (n) fasteners at no more than 12 in on center, near the middle of the flange and next to the panel's high rib.
  • Steel: (o) Fu/Fy ≥ 1.08.

Three more rules: where adjacent spans differ by more than 20 percent, those bays take the simple-span R. For simple spans, R is multiplied by r = 1.00 − 0.01ti (Eq. I6.2.1-2), with ti the uncompressed insulation thickness in inches. And §I6.2.1 does not apply to cantilevers, or to a continuous beam "for the region between inflection points adjacent to a support". That region is checked by Chapter F, as in the gravity case.

The example meets (a) to (h): its depth/thickness is 94, its depth/flange width 3.2, and its laps are 3.0 times the depth. ColdCalc checks those from the geometry and lists (i) to (o) for the designer to confirm. Under 0.9D + W (Wind uplift), the uplift moment peaks at 40.8 kip·in, about 9 ft from each end support. With Mno = 148.6 kip·in, φR·Mno = 0.90 × 148.6 × 0.70 = 93.6 kip·in, a ratio of 0.44.

Standing seam roofs fall under §I6.2.2, which refers to the country appendices. Appendix A (United States and Mexico) uses discrete point bracing with §F3, or Mn = R·Mno with R from tests to AISI S908; Appendix B (Canada) requires discrete bracing. ColdCalc implements §I6.2.1 only.

Anti-roll bracing and anchorage#

Every purlin on a slope tries to move sideways: a Z because of its Ixy, a C because its shear center is off the web, and both because of the down-slope component of gravity. The panel restrains each purlin, but the forces add up across all the purlin lines and must reach the frame. That is the job of anti-roll anchorage: clips, straps or braces near the top flange that take the force out of the roof plane.

S100-24 §I6.4.1 sets the requirements for purlin roofs under gravity with the top flange connected to metal sheathing:

  • an anchorage device in each purlin bay, connected at or near the top flange, with a path for forces from purlin lines that are not connected directly;
  • a design force PL from Eqs. I6.4.1-1 and I6.4.1-2. The lateral force from each purlin depends on its load, span, Ixy/Ix (zero for a C), the shear-center offset m (zero for a Z), the flange width and thickness, which way the top flange faces (up-slope or down-slope), and the roof slope;
  • a minimum stiffness (Eq. I6.4.1-7), and top flange lateral displacement between lines of anchorage no more than L/360 under ASD loads.

A rational analysis may replace these equations if it accounts for slope, torsion, the panel's restraint and the anchorage stiffness. §I6.4.2 instead allows torsional braces in the span with lateral restraint at the frame line, limiting the top flange displacement there to d/(20Ω) under ASD or φd/20 under LRFD (Ω = 2.0, φ = 0.75), and to L/180 between frame lines.

In ColdCalc a brace stops sideways movement and twist at a point, which shortens the lateral-torsional buckling length and restrains torsion; the analysis reports each brace force. ColdCalc does not yet design the §I6.4 anchorage itself.

Web crippling over the supports (§G5 and §H3)#

At an end support, the reaction bears on a single web near the member end: the end one-flange case of Table G5-3 for single-web Z-sections. Here the end reaction of 1.10 kip uses 0.39 of the available 2.80 kip.

At the interior support the reaction meets the largest moment, and §H3 checks the two together. For a single unreinforced web it is Eq. H3-1, 0.91(P/Pn) + M/Mno ≤ 1.33φ. Over a lap, though, the two Z-sections are nested and bolted together, and §H3(c) gives them their own, more generous interaction:

0.86(P/Pn) + M/Mno ≤ 1.65φ, with φ = 0.90
Eq. H3-3b

where Mno is the §F3 strength with Mne = My. Eq. H3-3 applies when h/t ≤ 150, N/t ≤ 140, Fy ≤ 70 ksi and R/t ≤ 5.5, with the thicker of the two parts no more than 1.3 times the thinner, and when the laps are bolted through the webs and to the support with the webs in contact. ColdCalc checks the dimensional limits and assumes the bolting of a standard lap. It shares the reaction equally between the two members and checks each against its own strengths; outside the limits it falls back to Eq. H3-1 for each and says so. Here each member takes 2.00 kip and 62.9 kip·in, so P/Pn = 0.32 and M/Mno = 0.42. The left side is 0.70 against 1.485, a ratio of 0.47. The web crippling article covers the load cases and coefficients in detail.

Lap modelling choices#

The Specification does not say how to model a lap. ColdCalc treats the lapped members as bending together over the full lap, without composite action: their E·I, G·J and E·Cw add, and each force is shared by the matching stiffness (bending by E·I, St. Venant torque by G·J, warping torque and bimoment by E·Cw). Each member is checked for its share, and a reaction inside a lap is shared equally for web crippling. A rigid lap is an idealization, so test the sensitivity when a lap is short or loosely bolted. The table changes one choice at a time:

ModelGoverning strength checkWhereRatio
As set up: 2 ft laps each way, braces at mid-span, R = 0.7Bending, strong axisat the end of the lap, 24 in past the interior support; 1.2D + S0.97
No lap: one member continuous over the supportBending, strong axisover the interior support; 1.2D + S1.30
3 ft laps each wayBending and torsion combinedat the end of the lap, 36 in past the interior support; 1.2D + S0.79
Inflection points taken as brace pointsBending, strong axisat the end of the lap, 24 in past the interior support; 1.2D + S0.66
No R factor: uplift checked as lateral-torsional bucklingBending and torsion combined9.0 ft from an end support; 0.9D + W (Wind uplift)1.07
No mid-span bracesBending, strong axisat the end of the lap, 24 in past the interior support; 1.2D + S3.80
The same purlin and loads with one modelling choice changed at a time: the highest strength ratio and where it occurs. Computed by ColdCalc to AISI S100-24, LRFD.

Read it as a list of decisions, not a ranking:

  • Laps carry the support region. Without one, the support section takes the full negative moment alone and fails. A longer lap moves the critical section to a lower moment.
  • The inflection-point assumption is worth a lot, which is why it needs a real brace behind it, not just zero moment.
  • The R factor matters for uplift. Without it the free flange is checked for lateral-torsional buckling between braces, ignoring the panel's restraint, and the purlin fails.
  • Braces carry the gravity design. Without them the bottom flange near the support is unbraced for the whole span. That check ignores the panel's restraint of the tension flange, so it is conservative; a rational analysis under §I6.1 can include it.

Reactions#

The analysis also gives the reactions the rafters and clips must carry. Under uplift they pull the purlin off its supports:

CombinationLeft endInteriorRight end
1.2D + S1.104.001.10
0.9D + W (Wind uplift)-0.75-2.71-0.75
Vertical support reactions per purlin, kip, upward positive (a negative value pulls the purlin off the support). Computed by ColdCalc.

Connections are outside ColdCalc's scope today, so take these to the clip or bolt design.

Where does a lapped Z-purlin usually fail?

Under gravity, usually at the end of the lap near an interior support: one member there carries the full negative moment with its bottom flange in compression and unbraced up to the next brace. Under uplift, the critical region is near mid-span, where the free bottom flange is in compression and Section I6.2.1 applies. Web crippling with bending (Section H3) is checked over the supports.

What is the R factor for continuous Z-purlins?

AISI S100-24 Table I6.2.1-1 gives R = 0.70 for continuous Z-sections and 0.60 for continuous C-sections. For simple spans R is 0.70 up to 6.5 in deep, 0.65 from 6.5 to 8.5 in, and 0.50 (Z) or 0.40 (C) from 8.5 to 12 in. The nominal strength is Mn = R·Mno, valid only within the limits (a) to (o) of Section I6.2.1.

Can I use the R factor between the inflection point and the support?

No. Section I6.2.1 does not apply to a continuous beam for the region between the inflection points adjacent to a support, nor to a cantilever. That region is checked with Chapter F, with the unbraced length set by braces, not by the inflection point.

How long should a purlin lap be?

To use the I6.2.1 R factor for a continuous system, each lap must extend at least 1.5 times the member depth from the center of the support in each direction (condition g). Beyond that minimum, a longer lap moves the critical lap-end section to a lower moment, so lap length is also a strength decision.

Do I need to check torsion in Z-purlins?

Yes, except where the R factor of Section I6.2.1 is used. Load on the top flange of a sloped roof acts away from the shear center and twists the purlin. Section H4 combines bending with the warping bimoment from Section G8.1. It does not apply with Sections I6.2.1 or I6.2.2, because those R values come from tests that included torsion.

Numbers in this article are computed by the ColdCalc engine when the page is built, so they match what the calculator gives today. AISI S100-24 is the governing text; ColdCalc is a design aid, and its results should be reviewed by the engineer responsible for the design.