1000S250-54 stud properties and strength

SSMA 10 in stud or joist, 2-1/2 in flange, 54 mil (0.0566 in), Grade 50 (ASTM A1003 ST50H). Gross and effective properties, finite strip buckling loads and available strengths to AISI S100-24, computed by the ColdCalc engine.

The 1000S250-54 has an area of 0.896 in² and weighs 3.05 lb/ft. Its strong-axis moment of inertia is 12.677 in⁴ gross and 10.599 in⁴ effective at yield, and its effective section modulus is 1.882 in³. With the flange braced, its allowable moment is 53.3 kip·in (ASD), governed by distortional buckling (§F4).

10″2-1/2″0.625″ lipt = 0.0566″

Dimensions

Depth10in
Flange width2-1/2in
Lip length0.625in
Design thickness0.0566in
Minimum thickness0.0538in
Inside bend radius0.0849in
Yield stress Fy50ksi
Tensile strength Fu65ksi

Gross properties

Area A0.896in²
Weight3.05lb/ft
Ix12.677in⁴
Sx2.535in³
rx3.762in
Iy0.653in⁴
Sy0.339in³
ry0.854in

Torsion and effective section

J0.957×10⁻³ in⁴
Cw12.472in⁶
xo-1.498in
ro4.138in
β0.869
Ixe at yield10.599in⁴
Sxe1.882in³

Effective properties: AISI S100-24 Appendix 1, strong-axis bending with the extreme fiber at Fy.

Available strength (AISI S100-24)

ActionNominalASD, Rn/ΩLRFD, φRnGoverned by
Strong-axis moment, flange braced (DSM)89.0853.3480.17§F4 · kip·in
Strong-axis moment, flange braced (EWM)89.0653.3380.15§F4 · kip·in
Shear, web without holes4.362.613.93§G2.1 · kip
Axial, 8 ft tall, braced at 4 ft (DSM)14.337.9612.18§E3.2 · kip
Axial, 9 ft tall, braced at 4 ft (DSM)14.337.9612.18§E3.2 · kip
Axial, 10 ft tall, braced at 4 ft (DSM)14.337.9612.18§E3.2 · kip
Axial, 12 ft tall, braced at 4 ft (DSM)14.337.9612.18§E3.2 · kip
Axial, 14 ft tall, braced at 4 ft (DSM)14.337.9612.18§E3.2 · kip
Axial, 16 ft tall, braced at 4 ft (DSM)14.337.9612.18§E3.2 · kip

Axial: pinned ends, weak-axis and torsional bracing every 48 in, concentric load. No holes. Bending and axial load together, unbraced flanges, web crippling and deflection depend on the member: check them in the calculator.

Elastic buckling

0.00.51.01.52.01101001000half-wavelength, in (log scale)load factor (P/Py)Local0.10 at 7.5 inDistortional (by cFSM)0.19 at 28.3 in
Signature curve of the 1000S250-54 in pure compression: the elastic buckling load, as a multiple of the yield load Py, at each buckle half-wavelength. The marked points are the local (Pcrℓ) and distortional (Pcrd) buckling loads; the distortional mode has no distinct minimum here, so it was identified by its modal participation (cFSM). The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.
0.00.51.01.52.01101001000half-wavelength, in (log scale)load factor (M/My)Local0.55 at 5.4 inDistortional0.68 at 23.0 in
Signature curve of the 1000S250-54 in strong-axis bending: the elastic buckling load, as a multiple of the yield moment My, at each buckle half-wavelength. The marked points are the local (Mcrℓ) and distortional (Mcrd) buckling loads, each a minimum of the curve. The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.

Finite strip results

Py44.80kip
Pcrℓ at 7.54.51kip
Pcrd at 28.38.62kip
My126.77kip·in
Mcrℓ at 5.469.49kip·in
Mcrd at 23.086.62kip·in

Signature curve minima, labelled by modal participation (cFSM). Half-wavelengths in inches.

Local
4.51 kip at 7.5 in
Distortional
8.62 kip at 28.3 in
Buckled shapes of the 1000S250-54 in compression, from the same finite strip analysis. Local buckling ripples the flat walls with the corners staying put; distortional buckling rotates a flange and its lip about the web–flange corner.

Quick answers

What does 1000S250-54 mean?

1000S250-54 is an SSMA designation: 10 in stud or joist, 2-1/2 in flange, 54 mil (0.0566 in). The first number is the depth in hundredths of an inch, the letter is the style (S for a stud or joist with lips, T for track), the next number is the flange width in hundredths of an inch, and the last is the minimum thickness in mils. The design thickness is 0.0566 in.

What are the section properties of a 1000S250-54 stud?

Area 0.896 in², weight 3.05 lb/ft, Ix 12.677 in⁴, Sx 2.535 in³, rx 3.762 in, Iy 0.653 in⁴, ry 0.854 in, J 0.957 ×10⁻³ in⁴, Cw 12.472 in⁶, computed by ColdCalc with rounded corners.

What is the allowable moment of a 1000S250-54?

With the compression flange braced against lateral-torsional buckling and Fy = 50 ksi, AISI S100-24 gives a nominal strong-axis moment of 89.1 kip·in by the Direct Strength Method (governed by §F4): 53.3 kip·in allowable (ASD) or 80.2 kip·in design strength (LRFD). Unbraced lengths, holes and combined loads reduce it.

What are the local and distortional buckling loads of a 1000S250-54?

By finite strip analysis, local buckling in compression occurs at 4.51 kip (half-wavelength 7.5 in) and distortional buckling at 8.62 kip (28.3 in), against a squash load Py of 44.80 kip.

Other 10 in studs

Computed by the ColdCalc engine from the SSMA dimensions (design thickness, lip length and bend radius as in the SSMA conventions), E = 29,500 ksi, with rounded corners. Manufacturers' published values can differ slightly in rounding and corner modelling; ColdCalc's effective section modulus is within 3 % of the SSMA tables for all 775 studs and tracks compared. Results must be reviewed by a qualified engineer. Validation