362S125-27 stud properties and strength

SSMA 3-5/8 in stud or joist, 1-1/4 in flange, 27 mil (0.0283 in), Grade 33 (ASTM A1003 ST33H). Gross and effective properties, finite strip buckling loads and available strengths to AISI S100-24, computed by the ColdCalc engine.

The 362S125-27 has an area of 0.176 in² and weighs 0.60 lb/ft. Its strong-axis moment of inertia is 0.347 in⁴ gross and 0.313 in⁴ effective at yield, and its effective section modulus is 0.163 in³. With the flange braced, its allowable moment is 2.9 kip·in (ASD), governed by distortional buckling (§F4).

3-5/8″1-1/4″0.188″ lipt = 0.0283″

Dimensions

Depth3-5/8in
Flange width1-1/4in
Lip length0.188in
Design thickness0.0283in
Minimum thickness0.0269in
Inside bend radius0.0796in
Yield stress Fy33ksi
Tensile strength Fu45ksi

Gross properties

Area A0.176in²
Weight0.60lb/ft
Ix0.347in⁴
Sx0.192in³
rx1.404in
Iy0.031in⁴
Sy0.032in³
ry0.416in

Torsion and effective section

J0.047×10⁻³ in⁴
Cw0.072in⁶
xo-0.770in
ro1.654in
β0.784
Ixe at yield0.313in⁴
Sxe0.163in³

Effective properties: AISI S100-24 Appendix 1, strong-axis bending with the extreme fiber at Fy.

Available strength (AISI S100-24)

ActionNominalASD, Rn/ΩLRFD, φRnGoverned by
Strong-axis moment, flange braced (DSM)4.802.874.32§F4 · kip·in
Strong-axis moment, flange braced (EWM)4.802.874.32§F4 · kip·in
Shear, web without holes1.070.640.96§G2.1 · kip
Axial, 8 ft tall, braced at 4 ft (DSM)2.071.151.76§E3.2 · kip
Axial, 9 ft tall, braced at 4 ft (DSM)2.071.151.76§E3.2 · kip
Axial, 10 ft tall, braced at 4 ft (DSM)2.061.151.75§E3.2 · kip
Axial, 12 ft tall, braced at 4 ft (DSM)2.041.141.74§E3.2 · kip
Axial, 14 ft tall, braced at 4 ft (DSM)1.981.101.68§E3.2 · kip
Axial, 16 ft tall, braced at 4 ft (DSM)1.790.991.52§E3.2 · kip

Axial: pinned ends, weak-axis and torsional bracing every 48 in, concentric load. No holes. Bending and axial load together, unbraced flanges, web crippling and deflection depend on the member: check them in the calculator.

Elastic buckling

0.00.51.01.52.01101001000half-wavelength, in (log scale)load factor (P/Py)Local0.28 at 2.8 inDistortional (by cFSM)0.40 at 9.1 in
Signature curve of the 362S125-27 in pure compression: the elastic buckling load, as a multiple of the yield load Py, at each buckle half-wavelength. The marked points are the local (Pcrℓ) and distortional (Pcrd) buckling loads; the distortional mode has no distinct minimum here, so it was identified by its modal participation (cFSM). The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.
0.00.51.01.52.02.53.03.51101001000half-wavelength, in (log scale)load factor (M/My)Local1.47 at 2.1 inDistortional0.90 at 7.5 in
Signature curve of the 362S125-27 in strong-axis bending: the elastic buckling load, as a multiple of the yield moment My, at each buckle half-wavelength. The marked points are the local (Mcrℓ) and distortional (Mcrd) buckling loads, each a minimum of the curve. The falling branch on the right is global buckling. Finite strip analysis by ColdCalc, simply supported ends, E = 29,500 ksi.

Finite strip results

Py5.82kip
Pcrℓ at 2.81.66kip
Pcrd at 9.12.31kip
My6.32kip·in
Mcrℓ at 2.19.29kip·in
Mcrd at 7.55.72kip·in

Signature curve minima, labelled by modal participation (cFSM). Half-wavelengths in inches.

Local
1.66 kip at 2.8 in
Distortional
2.31 kip at 9.1 in
Buckled shapes of the 362S125-27 in compression, from the same finite strip analysis. Local buckling ripples the flat walls with the corners staying put; distortional buckling rotates a flange and its lip about the web–flange corner.

Quick answers

What does 362S125-27 mean?

362S125-27 is an SSMA designation: 3-5/8 in stud or joist, 1-1/4 in flange, 27 mil (0.0283 in). The first number is the depth in hundredths of an inch, the letter is the style (S for a stud or joist with lips, T for track), the next number is the flange width in hundredths of an inch, and the last is the minimum thickness in mils. The design thickness is 0.0283 in.

What are the section properties of a 362S125-27 stud?

Area 0.176 in², weight 0.60 lb/ft, Ix 0.347 in⁴, Sx 0.192 in³, rx 1.404 in, Iy 0.031 in⁴, ry 0.416 in, J 0.047 ×10⁻³ in⁴, Cw 0.072 in⁶, computed by ColdCalc with rounded corners.

What is the allowable moment of a 362S125-27?

With the compression flange braced against lateral-torsional buckling and Fy = 33 ksi, AISI S100-24 gives a nominal strong-axis moment of 4.8 kip·in by the Direct Strength Method (governed by §F4): 2.9 kip·in allowable (ASD) or 4.3 kip·in design strength (LRFD). Unbraced lengths, holes and combined loads reduce it.

What are the local and distortional buckling loads of a 362S125-27?

By finite strip analysis, local buckling in compression occurs at 1.66 kip (half-wavelength 2.8 in) and distortional buckling at 2.31 kip (9.1 in), against a squash load Py of 5.82 kip.

Other 3-5/8 in studs

Computed by the ColdCalc engine from the SSMA dimensions (design thickness, lip length and bend radius as in the SSMA conventions), E = 29,500 ksi, with rounded corners. Manufacturers' published values can differ slightly in rounding and corner modelling; ColdCalc's effective section modulus is within 3 % of the SSMA tables for all 775 studs and tracks compared. Results must be reviewed by a qualified engineer. Validation